KEB COMBIVERT F5-A Applications Manual page 78

Table of Contents

Advertisement

Operating and appliance data
Parameter
ru.22
internal input state
Display of the digital external and internal inputs set currently. The input is only regarded as set if it is available
as effective signal to the further processing (i.e. accepted through strobe, edge-triggering or logic operation).
According to table like ru.21 a specific decimal value is given out for each digital input. If several inputs are
controlled, the sum of the decimal values (see ru.21) is indicated (also see Chapt. 7.3 „Digital inputs").
Parameter
ru.23
output condition state
With parameters do.0...do.7 switching conditions can be selected, that serve as a base for setting the outputs.
This parameter indicates which of the selected switching conditions are met before they are linked or inverted
by programmable logic (also see Chapt. 7.3. „Digital outputs"). According to following table a specific decimal
value is given out for the switching conditions. If several of the selected switching conditions are met, the sum
of the decimal values is indicated.
Parameter
State of output flags
ru.24
Display of the output flags after logic step 1. The selected switching conditions are linked in logic step 1
(do.08...24) and indicated here (see chapt. 7.3 „Digital outputs"). According to following table a specific decimal
value is given out for any output flags. If several output flags are set, the sum of the decimal values is indicated.
Page 7.1 - 8
COMBIVERT F5-A, -E, -H
Addr.
R
0216h RO
Addr.
0217h RO
Bit
Decimal
Output
-No.
value
0
1
Switching condition 0 (do.0)
1
2
Switching condition 1 (do.1)
2
4
Switching condition 2 (do.2)
3
8
Switching condition 3 (do.3)
4
16
Switching condition 4 (do.4)
5
32
Switching condition 5 (do.5)
6
64
Switching condition 6 (do.6)
7
128
Switching condition 7 (do.7)
Addr.
R
0218h RO
Bit
Decimal
Output
-No.
value
0
1
Flag 0
1
2
Flag 1
2
4
Flag 2
3
8
Flag 3
4
16
Flag 4
5
32
Flag 5
6
64
Flag 6
7
128
Flag 7
PG E
Min. value
-
-
0
R
PG E Min. value
-
-
0
PG E
Min. value
-
-
0
[?]
Max. value
Res.
4095
1
-
[?]
Max. value
Res.
255
1
-
[?]
Max. value
Res.
255
1
-
© KEB, 2012-10
Default
-
Default
-
Default
-