Output OC must therefore be set when the condition "target window reached" is not set.
→ do.31: Inv. flags for OC = 1: M0 OC = NOT M0
→ do.39: Flag selection for OC = 1: M0
block 0
Position = 0
Permitted max. speed = 1500 rpm
next positioning step defined in block 1
Wait for "start positioning" command
block 1
Position = first stopping point
speed up to the first stopping point
next positioning step defined in block 2
Wait for "start positioning" command
block 2
Position = second stopping point
speed up to the second stopping point
Back to start
Wait for "start positioning" command
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Posi- and synchronous operating
ru.61: target position
ru.56: Set position
„Start positioning"
signal
of ext. control (I3)
automatic generated
„start
positioning" signal (IB)
ru.43: timer 1 display
„target reached" signal
ru.60: act. position
index
→ PS.23: Index / selection = 0
→ PS.24: Index / position = 0
→ PS.25 = 1500 rpm
→ PS.26 = 1
→ PS.27 = 0: no + absolute
→ PS.23: Index / selection = 1
→ PS.24: Index / position = 100.000
→ PS.25 = 1000 rpm
→ PS.26 = 2
→ PS.27 = 0: no + absolute
→ PS.23: Index / selection = 2
→ PS.24: Index / position = 200.000
→ PS.25 = 1000 rpm
→ PS.26 = 0
→ PS.27 = 0: no + absolute
7
Page 7.12 - 51