Digital in- and outputs
Select switching conditions
Adjust do.16 to „1" (evaluate switching condition of do.0 ),
Adjust do.17 to „2" (evaluate switching condition of do.1),
Adjust do.18 to „4" (evaluate switching condition of do.2),
Adjust do.8, do.9 and do.10 to „0" (no inversion).
The adjustment of do.24 is independent for this example, as only one condition each is adjusted at do.16...18.
Adjust flags
Output O1 (terminal X2A.18)
Set do.33 to „7"(evaluate flags 1...3)
Adjust do.25 to „1"(flag 1 is inverted, it means that the condition is fulfilled if the inverter does not accelerate).
Adjust do.41 to „1" (the flags selected with do.33 are AND connected)
Output O2 (terminal X2A.19)
Adjust do.34 to „1" (flag 1 is evaluated).
Adjust do.26 to „0" (no inversion)
The adjustment of do.41 is independent for this example, since only one flag is adjusted in do.34.
Relay output R1 (terminal X2A.24...26)
Adjust do.35 to „2"(flag 2 is evaluated).
do.27 to „0" (no inversion)
The adjustment of do.41 is independent for this example, since only one flag is adjusted in do.35.
Relay output R2 (terminal X2A.27...29)
Adjust do.36 to „4"(flag 3 is evaluated).
7
do.28 to „0" (no inversion)
The adjustment of do.41 is independent for this example, since only one flag is adjusted in do.36.