Input of the motor data
Values dr.00 to dr.05 must be taken from the motor name plate.
The value for dr.06 can be identified automatically (see point
6).
⇒ dr.00 DASM rated current
⇒ dr.01 DASM rated speed
⇒ dr.02 DASM rated voltage
⇒ dr.04 DASM cos phi
⇒ dr.05 DASM rated frequency
⇒ dr.06 DASM stator resistance
6.
Measurement of the stator resistance
The stator resistance dr.06 can be determined automatically
by the KEB COMBIVERT.
Inverter must be in status „70: standstill (modulation off)". Start
measurement with the input of
dr.06 = 250000: on
start
Open control release (X2A.16) after measurement
7.
Calculation of motor-dependent data
Activation of SMM, as well as the adaption of the v/f characte-
ristic is made by the input of:
⇒ Fr.10 load motor-dep. parameter = 3
8.
Adjust speed controller
The speed controller must be adapted to the application via
cS.06 and cS.09.
Enter application specific data
9.
e.g. limit values (speed limits, torque limits etc.),
acceleration- / deceleration ramps,
function of the digital in- / outputs,
Type of speed setpoint setting etc.
10.
Test run
Test run, in order to check whether the drive runs stable in all
speed ranges and under all load conditions and if a sufficient
safety distance to the current- and load limits is available etc.
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Start-up
Proper data for the adaption of the in-
verter to the respective application can
be find in the corresponding chapters.
Page 6.2 - 5