If the modulation is switched off, the break control output is immediately deactivated so that the brake closes.
In all other cases, the sequence is as follows:
Pn.39: Brake delay time
After switching off the rotation setting, the drive runs to the stop speed Pn.41 (this parameter must contain
value 0 rpm for vector controlled drives) and waits there for the duration of the brake delay time.
Pn.40: Brake closing time
Afterwards, the brake control output is deactivated and the brake takes over the load during the brake
closing time. The inverter remains during this time on stop speed Pn.41.
Pn.38: Brake fadeout time
After expiration of the brake closing time (Pn.40), the fadeout time expires. During this time, the current is
lowered to 0. After expiration of the fadeout time, the modulation remains switched on for another 100 ms.
Thereby, the noise that can occur in the motor during a jolt-like shutdown of the current can be prevented.
After the current has been drained, the inverter changes into the status "70: standstill (Modulation off)"
(LS)
The following figure shows the sequence of the brake control without fadeout time. In vector controlled system,
the start- and the stop-value (Pn.37 / Pn.41) must be set to 0 rpm.
Figure 7.15.5.3 Brake control
Reference
(ru.01)
Stop value
(Pn.41)
Start value
(Pn.37)
Set direction
of rotation for
Inverter
LS
state
opened
brake
closed
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
boff
boff
boff
facc
fcon
fcon
premagneti-
Brake re-
sing time
lease time
Pn.35
Pn.36
Special functions
Actual speed
facc
facc
fdec
bon
bon
fcon
fcon
Brake delay
Brake clo-
time
sing time
Pn.40
Pn.40
Page 7.15 - 15
7
LS