10: High resolution in %
(ru.63)
Other functions like quick stop, fixed frequency, or positioning have priority over "standard operation" and can
therefore lead to different speed setpoints than selected in oP.00 .
The following speed setpoint limiting blocks can change the setpoint.
Direct analog setpoint setting (AN1 direct)
The cycle time of the software is 1 ms. During this time the analog input/output status is updated once. Addi-
tionally the inverter requires a processing time of 1... 3 ms before the new setpoint value is calculated. If the
inverter is used as secondary final control element of a superior control, this time can impair the dynamics of
the entire closed-loop control system.
In such cases the analog setpoint value can be processed directly to the control processor (direct setpoint
adjustment). Thus a scan time of 250 µs is possible. To enable this fast response to an analog setpoint value,
some restrictions must be accepted:
The calculation formula of the analog setpoint value changes. Parameters oP.06 / oP.07 are without influence
on the setpoint calculation.
percentage analog value = (analog value/10V x 100% - An.06) x An.05
This value is limited to+/- 100%.
n
= limited analog value in percent x oP.10
set
This value is limited with oP.14 for for both directions of rotation.
The reference limitations oP.06 / oP.07 / oP.11 do not have any function; the absolute max. reference is only
limited by oP.14 (for both directions).
The acceleration / deceleration and S-curve time have no effect; it is operated internally without ramps.
The parameters An.01...04 and An.07...09 are without any function
The stop position controller cannot be activated.
High resolution reference setting
The setpoint setting with the settings oP.00 = 0...9 is 16 Bit wide. This results in a maximum resolution of 0.125
rpm in 4000-rpm mode (ud.02 = 4 and 8).
For applications needing a higher resolution, the high resolution setpoint setting was introduced. Here, the
setpoint is set as a 32-Bit-value.
Since only a 16-Bit-value can be output, the low-order 16 bits of the ramp output value are upsampled. On
overrun, the base value is increased for one cycle (1 ms) (by 0.125 rpm in 4000-rpm mode). These setpoint
fluctuations are smoothed mechanically, leading to the higher average resolution.
To achieve the highest possible resolution for the application, two parameters can be used:
oP.64 Ref. value high-resolution
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Setpoint, rotation- and ramp setting
Setting of the speed setpoint value
via oP.63 "reference value high-reso-
lution". This mode must be used if the
standard speed resolution is insuffici-
ent.
Configuration of the high resolution
and calculation of the speed setpoint
from parameters oP.63 / oP.64 see in-
structions.
Page 7.4 - 5