01/2007
6.3.7

Parameterizing the MPI interface (X102) (optional)

Dialog box
6.3.8
Parameterization of the communications processor (CP 840D sl)
(Ethernet)
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) – 01/2007 Edition
Dialog box: Properties – New PROFIBUS Subnet
Tab: Network settings
Transmission rate: <Trans.rate>
Profile: DP
OK
Tab: Mode
Radio button: <Mode>
OK
OK
When you have completed the "Properties – PROFIBUS DP Interface" dialog
box (see previous Section 6.3.5, Page 6-143) the 840Di sl Rack is displayed in
the Station window.
To parameterize the MPI interface you will have to make the following parame-
ter settings:
S
Interface type
S
Transmission rate
Double–click module: MPI/DP, slot X1 in the 840Di sl Rack, to open the MPI/DP
Properties dialog box.
Dialog box: MPI/DP Properties
Tab: General
Group box: Interface
Type: MPI
Button: "Properties..."
Dialog box: Properties – MPI Interface MPI/DP
Tab: Parameter
Address: 2 (see note)
Subnet: MPI(1)
OK
OK
Notice
With SINUMERIK 840Di sl, the MPI address of the PLC must always be set
to 2.
For the parameterization of the integrated communications processor:
"CP 840D sl", the following parameters have to be set:
S
IP address of the PCU
S
Subnet mask of the PCU
6 PLC Commissioning
6.3 Creating a SIMATIC S7 project
187.5 kbaud
6-145