3.13. Main Menu - Smart Logic - Group 13

3.13.1. 13-** Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user defined actions (see par. 13-52 [x]) executed by the SLC when the associated user defined
event
(see par. 13-51 [x]) is evaluated as TRUE by the SLC. Events and
event
[0] is fulfilled (attains the value TRUE),
action
[1] will be executed and so on. Only one
during the current scan interval and no other
each scan interval. Only when
events
actions
from 1 to 20
and
event
action
When the last
/
has been executed, the sequence starts over again from
event / actions:
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting
The SLC starts when the Start Event (defined in par. 13-01
stops when the
Stop Event
(par. 13-02) is TRUE. Par. 13-03 resets all SLC parameters and start programming from scratch.
3.13.2. 13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
13-00 SL Controller Mode
Option:
*
Off
[0]
[1]
On
13-01 Start Event
Option:
*
False
[0]
[1]
True
[2]
Running
[3]
In range
action
[0] is executed. After this, the conditions of
event
will be evaluated at any time. If an
events
will be evaluated. This means that when the SLC starts, it evaluates
event
[0] is evaluated TRUE, will the SLC execute
.
On
Off
[1] or
Start Event
Function:
Disables the Smart Logic Controller.
Enables the Smart Logic Controller.
Function:
Select the boolean (TRUE or FALSE) input to activate Smart Logic Control.
Enters the fixed value of FALSE in the logic rule.
Enters the fixed value TRUE in the logic rule.
See parameter group 5-3* for further description.
See parameter group 5-3* for further description.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
actions
are each numbered and linked together in pairs. This means that when
event
[1] will be evaluated and if evaluated TRUE,
event
is evaluated as FALSE, nothing happens (in the SLC)
action
[0] and start evaluating
event
action
[0] /
[0]. The illustration shows an example with three
[0] in par. 13-00. The SLC always starts in state 0 (where it evaluates
) is evaluated as TRUE (provided that
3. Parameter Description
event
[0] (and only
event
event
[1]. It is possible to programme
event
On
[1] is selected in par. 13-00). The SLC
3
[0])
[0]).
115