3. Parameter Description
3
There are two methods which can be employed, depending upon whether or not the Speed at System design Working Point is known.
Parameter used
Flow Compensation, 22-80
Square-Linear Curve Approximation,22-81
Work Point Calculation, 22-82
Speed at No Flow, 22-83/84
Speed at Design Point, 22-85/86
Pressure at No Flow, 22-87
Pressure at Rated Speed, 22-88
Flow at Design Point, 22-89
Flow at Rated Speed, 22-90
22-80 Flow Compensation
Option:
*
Disabled
[0]
[1]
Enabled
22-81 Square-Linear Curve Approximation
Range:
*
100%
[ 0 – 100%]
NB!
Please note: Not visible when running in cascade.
184
Speed at
Design Point
KNOWN
+
+
+
+
+
+
-
-
-
Function:
[0]
Disabled
: Set-Point compensation not active.
Enabled
[1]
:Set-Point compensation is active. Enabling this parameter allows Flow Compensated Setpoint op-
eration.
Function:
Example 1:
Adjustment of this parameter allows the shape of the control curve to be adjusted.
0 = Linear
100% = Ideal shape (theoretical).
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
Speed at
Design Point
Cascade Controller
UNKNOWN
+
+
+
+
-
+
+
+
+
+
-
-
-
-
+
-
-
-