3. Parameter Description
15-07 Reset Running Hours Counter
Option:
*
Do not reset
[0]
[1]
Reset counter
3
15-08 Numbers of Starts
Range:
[0 - 2147483647]
NB!
This parameter will be reset when resetting
3.15.3. Data Log Settings, 15-1*
The Data Log enables continuous logging of up to 4 data sources (par. 15-10) at individual rates (par. 15-11). A trigger event (par. 15-12) and window
(par. 15-14) are used to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
None
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status Word
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor Current
[1616]
Torque [Nm]
[1617]
Speed [RPM]
[1618]
Thermal Motor Load
[1622]
Torque [%]
[1630]
DC Link Voltage
[1632]
Brake Energy / s
[1633]
Brake Energy / 2 min
[1634]
Heatsink Temp.
[1635]
Thermal Drive Load
[1650]
External Reference
[1652]
Feedback [Unit]
[1654]
Feedback 1 [Unit]
[1655]
Feedback 2 [Unit]
[1656]
Feedback 3 [Unit]
134
Function:
Do not reset
Select
[0] if no reset of the Running Hours counter is desired.
Reset counter
Select
[1] and press [OK] to reset the Running Hours counter (par. 15-01) and
of Starts
, to zero (see also par. 15-01).
Function:
This is a read out parameter only. The counter shows the numbers of starts and stops caused by a normal Start/
Stop command and/or when entering/leaving sleep mode.
par. 5-07 Reset Running Hours counter
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
par. 15-08 Numbers
.