6-02 Fire Mode Live Zero Timeout Function
Option:
[0]
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
3.8.3. 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
*
0.07V
[0.00 - par. 6-11]
6-11 Terminal 53 High Voltage
Range:
*
10.0V
[Par. 6-10 to 10.0 V]
6-12 Terminal 53 Low Current
Range:
*
4 mA
[0.0 to par. 6-13 mA]
6-13 Terminal 53 High Current
Range:
*
20.0 mA
[ Par. 6-12 to 20.0 mA]
Function:
The function set in par. 6-01 will be activated if the input signal on analogue inputs is below 50% of the value
in par. "Terminal xx Low Current/Voltage" for a time period defined in par. 6-00.
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/feedback
value set in par. 6-14.
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high reference/feedback
value set in par. 6-15.
Function:
Enter the low current value. This reference signal should correspond to the low reference/feedback value, set in
par. 6-14. The value must be set at >2 mA in order to activate the Live Zero Time-out Function in par. 6-01.
Function:
Enter the high current value corresponding to the high reference/feedback set in par. 6-15.