Danfoss VLT FC 100 Series Programming Manual page 205

Hvac drive
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

®
VLT
HVAC Drive Programming Guide
[171]
2
lb/in
[172]
in WG
[173]
ft WG
[180]
HP
24-03 Fire Mode Min Reference
Range:
*
0
[-999999.999 to +999999.999]
24-04 Fire Mode Max Reference
Range:
*
1500
[-999999.999 to
+999999.999]
24-05 Fire Mode Preset Reference
Range:
*
0%
[-100% to +100%]
24-06 Fire Mode Reference Source
Option:
*
No Function
[0]
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[20]
Digital Potentiometer
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog input X42/1
[24]
Analog input X42/3
[25]
Analog input X42/5
24-07 Fire Mode Feedback Source
Option:
*
No Function
[0]
[1]
Analog input 53
Function:
Minimum value for the reference/set point (limiting the sum of value in
and value of signal on input selected in
If running in Open loop when Fire Mode is active, the unit is chosen by the setting of
Unit
. For closed loop, the unit is selected in
Function:
Maximum value for the reference/set point (limiting the sum of value in
ence
and value of signal on input selected in
If running in Open loop when Fire Mode is active, the unit is chosen by the setting of
Unit
. For closed loop, the unit is selected in
Function:
Enter the required preset reference/set point as a percentage of the Fire Mode Max Reference set in par. 24-04.
The set value will be added to the value represented by the signal on the analog input selected in
Fire Mode Reference Source
.
Function:
Select the external reference input to be used for the Fire Mode. This signal will be added to the value set in
par. 24-05, Fire Mode Preset Reference
Function:
Select the feed back input to be used for the Fire Mode feed back signal when Fire Mode is active.
If the motor also is controlled by the built in PID controller when in normal operation, the same transmitter can
be used for both cases by selecting the same source.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
par. 24-05, Fire Mode Preset Reference
par. 24-06, Fire Mode Reference Source
par. 24-02, Fire Mode Unit
.
par. 24-05, Fire Mode Preset Refer-
par. 24-06, Fire Mode Reference Source
par. 24-02, Fire Mode Unit
.
.
3. Parameter Description
).
par. 0-02, Motor Speed
).
par. 0-02, Motor Speed
par. 24-06,
205