VLT
HVAC Drive Programming Guide
3.7.8. 5-6* Pulse Outputs
Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated to terminals 27 or 29. Select terminal 27
output in par. 5-01 and terminal 29 output in par. 5-02.
Options for readout output variables:
*
No operation
[0]
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque relative to limit
[105]
Torque relative to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop
[114]
Ext. Closed Loop
[115]
Ext. Closed Loop
5-60 Terminal 27 Pulse Output Variable
Option:
*
No operation
[0]
5-62 Pulse Output Maximum Frequency #27
Range:
*
5000Hz
[0 - 32000 Hz]
Function:
Same options and functions as par. 5-6*
Select the operation variable assigned for terminal 27 readouts.
This parameter cannot be adjusted while the motor is running.
Function:
Set the maximum frequency for terminal 27, corresponding to the output variable selected in par. 5-60.
This parameter cannot be adjusted while the motor is running.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3. Parameter Description
Pulse Outputs
.
3
77