3. Parameter Description
14-22 Operation Mode
Option:
*
Normal operation
[0]
3
[1]
Control card test
[2]
Initialisation
14-25 Trip Delay at Torque Limit
Range:
*
60 s
[0 - 60 s = OFF]
128
Function:
Use this parameter to specify normal operation, to perform tests or to initialise all parameters except par. 15-03,
15-04 and 15-05. This function is active only when the power is cycled (power off-power on) to the frequency
converter.
Normal operation
Select
[0] for normal operation of the frequency converter with the motor in the selected
application.
Select
Control card test
[1] to test the analog and digital inputs and outputs and the +10 V control voltage. The
test requires a test connector with internal connections.
Use the following procedure for the control card test:
1.
Select
Control card test
[1].
2.
Disconnect the mains supply and wait for the light in the display to go out.
3.
Set switches S201 (A53) and S202 (A54) = 'ON' / I.
4.
Insert the test plug (see below).
5.
Connect to mains supply.
6.
Carry out various tests.
7.
The results are displayed on the LCP and the frequency converter moves into an infinite loop.
8.
Par. 14-22 is automatically set to Normal operation. Carry out a power cycle to start up in Normal
operation after a control card test.
If the test is OK:
LCP read-out: Control Card OK.
Disconnect the mains supply and remove the test plug. The green LED on the control card will light up.
If the test fails:
LCP read-out: Control Card I/O failure.
Replace the frequency converter or control card. The red LED on the control card is turned on. To test the plugs,
connect/group the following terminals as shown below: (18 - 27 - 32), (19 - 29 - 33) and (42 - 53 - 54).
Select
Initialization
[2] to reset all parameter values to default settings, except for par. 15-03, 15-04, and 15-05.
The frequency converter will reset during the next power-up.
Par. 14-22 will also revert to the default setting
Function:
Enter the torque limit trip delay in seconds. When the output torque reaches the torque limits (par. 4-16 and
4-17), a warning is triggered. When the torque limit warning has been continuously present for the period speci-
fied in this parameter, the frequency converter trips. Disable the trip delay by setting the parameter to 60 s =
OFF. Thermal frequency converter monitoring will still remain active.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
Normal operation
[0].