Danfoss VLT FC 100 Series Programming Manual page 11

Hvac drive
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

®
VLT
HVAC Drive Programming Guide
Menu key
[Menu]
Select one of the following modes:
Status
Quick Setup
Main Menu
Main Menu is used for programming all parameters.
The parameters can be accessed immediately unless a password has been created via par. 0-60, 0-61, 0-65 or 0-66.
Quick Setup is used to set up the frequency converter using only the most essential parameters.
The parameter values can be changed using the up/down arrows when the value is flashing.
Select Main Menu by pressing the [Menu] key a number of times until the Main Menu LED is lit.
Select the parameter group [xx-__] and press [OK]
Select the parameter [__-xx] and press [OK]
If the parameter is an array parameter select the array number and press [OK]
Select the wanted data value and press [OK]
Navigation Keys
[Back]
for stepping backwards
Arrow [ ] [ ]
keys are used for manoeuvring between parameter groups, parameters and within parameters.
[OK]
is used for choosing a parameter marked by the cursor and for enabling the change of a parameter.
Operation Keys
Keys for local control are found at the bottom of the control panel.
[Hand on]enables control of the frequency converter via the LCP. [Hand on] also starts the motor and it is now possible to enter the motor speed data
by means of the arrow keys. The key can be selected as
External stop signals activated by means of control signals or a serial bus will override a 'start' command via the LCP.
The following control signals will still be active when [Hand on] is activated:
[Hand on] - [Off] - [Auto on]
Reset
Coasting stop inverse
Illustration 2.4: Display example
Illustration 2.5: Operation keys of the numerical CP (NLCP)
Enable
Disable
[1] or
[0] via par. 0-40
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
2. How to Programme
130BP046.10
[Hand on] Key on LCP
.
2
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt hvac drive fc 102

Table of Contents