16-30 DC Link Voltage
Range:
*
0V
[0 - 10000 V]
16-32 Brake Energy /s
Range:
*
0 kW
[0 to 675.000 kW]
16-33 Brake Energy /2 min
Range:
*
0.000kW
[0.000 - 500.000 kW]
16-34 Heatsink Temp.
Range:
*
0°C
[0 - 255 °C]
16-35 Inverter Thermal
Range:
*
0 %
[0 - 100 %]
16-36 Inv. Nom. Current
Range:
*
A
[0.01 - 10000 A]
16-37 Inv. Max. Current
Range:
*
[0.01 to 10000 A] View the inverter maximum current, which should match the nameplate data on the connected motor. The data
Size dependent
16-38 SL Controller State
Range:
*
0
[0 - 100]
16-39 Control Card Temp.
Range:
*
0°C
[0 - 100 °C]
16-40 Logging Buffer Full
Option:
*
No
[0]
[1]
Yes
Function:
View a measured value. The value is filtered with an 30 ms time constant.
Function:
View the brake power transmitted to an external brake resistor, stated as an instantaneous value.
Function:
View the brake power transmitted to an external brake resistor. The mean power is calculated on an average
basis for the most recent 120 seconds.
Function:
View the frequency converter heatsink temperature. The cut-out limit is 90 ± 5 °C, and the motor cuts back in
at 60 ± 5 °C.
Function:
View the percentage load on the inverter.
Function:
View the inverter nominal current, which should match the nameplate data on the connected motor. The data
are used for calculation of torque, motor protection, etc.
Function:
are used for calculation of torque, motor protection, etc.
Function:
View the state of the event under execution by the SL controller.
Function:
View the temperature on the control card, stated in °C.
Function:
View whether the logging buffer is full (see par. 15-1*). The logging buffer will never be full when
Logging Mode
Log always
is set to
[0].