3. Parameter Description
16-11 Power [HP]
Range:
*
0 HP
[0 to 1000 HP]
16-12 Motor Voltage
Range:
3
*
0.0V
[0.0 - 6000.0 V]
16-13 Motor Frequency
Range:
*
0.0Hz
[0.0 - 6500.0 Hz]
16-14 Motor Current
Range:
*
0 A
[0 to 1856 A]
16-15 Frequency [%]
Range:
*
0.00%
[-100.00 - 100.00 %]
16-16 Torque [Nm]
Range:
*
0.0Nm
[-3000.0 - 3000.0 Nm]
16-17 Speed [RPM]
Range:
*
0 RPM
[-30000 - 30000 RPM]
16-18 Motor Thermal
Range:
*
0 %
[0 - 100 %]
16-22 Torque
Range:
[-200% - 200%]
3.16.4. 16-3* Drive Status
Parameters for reporting the status of the frequency converter.
142
Function:
View the motor power in HP. The value shown is calculated on the basis of the actual motor voltage and motor
current. The value is filtered, and therefore approximately 30 ms may pass from when an input value changes
to when the data read-out values change.
Function:
View the motor voltage, a calculated value used for controlling the motor.
Function:
View the motor frequency, without resonance dampening.
Function:
View the motor current measured as a mean value, IRMS. The value is filtered, and thus approximately 30 ms
may pass from when an input value changes to when the data read-out values change.
Function:
View a two-byte word reporting the actual motor frequency (without resonance dampening) as a percentage
(scale 0000-4000 Hex) of par. 4-19
Max. Output Frequency
instead of the MAV.
Function:
View the torque value with sign, applied to the motor shaft. Linearity is not exact between 110% motor current
and torque in relation to the rated torque. Some motors supply more than 160% torque. Consequently, the min.
value and the max. value will depend on the max. motor current as well as the motor used. The value is filtered,
and thus approx. 1.3 seconds may pass from when an input changes value to when the data read-out values
change.
Function:
View the actual motor RPM.
Function:
View the calculated thermal load on the motor. The cut-out limit is 100%. The basis for calculation is the ETR
function selected in par.1-90.
Function:
This is a read out parameter only.
Shows the actual torque yielded in percentage of the rated torque, based on the setting of the motor size and
Motor Power [kW]
rated speed in
, par. 1-20 or
Broken Belt Function
This is the value monitored by the
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
. Set par. 9-16 index 1 to send it with the Status Word
Motor Power [Hp]
Motor Nominal Speed
, par. 1-21 and
set in par. 22-6*.
, par. 1-25.