3. Parameter Description
23-60 Trend Variable
Option:
*
Power [kW or HP]
[0]
3
[1]
Current [A]
[2]
Frequency [Hz]
[3]
Motor Speed [RPM]
23-61 Continuous Bin Data
Range:
*
0
[0 - 4.294.967.295]
23-62 Timed Bin Data
Range:
*
0
[0-4294967295]
23-63 Timed Period Start
Range:
*
2000-01-01 00:00
00:00 - 2099-12-31 23:59]
198
Function:
Select the desired operating variable to be monitored for Trending.
Power yielded to the motor. Reference for the relative value is the rated motor power programmed in
Motor Power [kW
] or
16-11, Power [Hp]
Output current to the motor. Reference for the relative value is the rated motor current programmed in
1-24, Motor Current
Output frequency to the motor. Reference for the relative value is the maximum output frequency programmed
in
par. 4-14, Motor Speed High Limit [Hz]
Speed of the motor. Reference for relative value is the maximum motor speed programmed in
Speed High Limit
.
Function:
Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between elements by
means of
and
10 counters with the frequency of occurrence for the operating variable monitored, sorted according to the
following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are the default limits. These can be changed in par. 23-65,
Bin Value
.
Starts to count when the frequency converter is powered up for the first time. All counters can be reset to 0 in
par. 23-66,
Reset Continuous Bin Data
Function:
Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between elements by
means of
and
10 counters with the frequency of occurrence for the operating data monitored sorted according to the intervals
Continuous Bin Data
as for par. 23-61,
Starts to count at the date/time programmed in par. 23-63,
programmed in par. 23-64,
Data
.
Function:
Set the date and time at which the Trending starts the update of the Timed Bin counters.
[2000-01-01
MG.11.C5.02 - VLT
par. 1-21, Motor Power [HP]
. Actual value can be read in
.
. Actual value can be read in
par. 16-14, Motor Current
Actual value can be read in
buttons on the LCP.
.
buttons on the LCP.
.
Timed Period Stop
. All counters can be reset to 0 in par. 23-67,
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
par. 16-10, Power [kW]
.
par. 16-13, Frequency
.
par. 4-13, Motor
Timed Period Start
, and stops at the time/date
Reset Timed Bin
par. 1-20,
or
par.
par.
Minimum