3. Parameter Description
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
3
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL digital out A
[81]
SL digital out B
[82]
SL digital out C
[83]
SL digital out D
[84]
SL digital out E
[85]
SL digital out F
3.9.4. 8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Option:
*
FC
[0]
[1]
FC MC
[2]
Modbus RTU
[3]
Metasys N2
[9]
FC option
NB!
Further details can be found in the BACnet and Metasys manuals.
92
Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the control card.
Parameter group 8-7* is only visible when FC Option [9] is chosen.
Communication according to the FC Protocol as described in the
lation and Set-up
.
FC
Same as
[0] but to be used when downloading SW to the frequency converter or uploading dll file (covering
information regarding parameters available in the frequency converter and their inter-dependencies) to Motion
Control Tool MCT10.
Communication according to the Modbus RTU protocol as described in the
Installation and Set-up
.
Communication protocol. The N2 software protocol is designed to be general in nature in order to accommodate
the unique properties each device may have. Please see separate manual
11.Gx.yy
.
To be used when a gateway is connected to the integrated RS-485 port, e.g. the BACnet gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and
on the network, e.g. BACnet.
VLT
®
HVAC Drive BACnet, MG.11.Dx.yy
Please see separate manual
-Baud rate for the FC port will be set to a fixed value (115.200 Baud) and
set the baud rate for the network port (e.g. BACnet) on the gateway.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
VLT HVAC Drive Design Guide, RS-485 Instal-
VLT HVAC Drive Design Guide, RS-485
VLT
par. 8-31 Address
, is now used to set the address for the gateway
.
par. 8-32 Baud Rate
®
HVAC Drive Metasys, MG.
, is now used to