3. Parameter Description
NB!
Changing the value of these parameters affects the setting of other parameters.
1-20 Motor Power [kW]
3
Range:
*
Size related
[0.09 - 1200 kW]
1-21 Motor Power [HP]
Range:
*
Size related
[0.09 - 900 HP]
1-22 Motor Voltage
Range:
*
Size related
[10 - 1000 V]
1-23 Motor Frequency
Range:
*
Size related
[20 - 1000 Hz]
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range:
*
Size related
[0.1 - 10000 A]
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
*
Size related
[100 - 60,000 RPM]
This parameter cannot be adjusted while the motor is running.
40
Function:
Enter the nominal motor power in kW according to the motor nameplate data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in par.
Regional Settings
, either par. 1-20 or par. 1-21
Function:
Enter the nominal motor power in HP according to the motor nameplate data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in par. 0-03
made invisible.
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Select the motor frequency value from the motor nameplate data. For 87 Hz operation with 230/400 V motors,
set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Reference
to the 87 Hz application.
Function:
Enter the nominal motor current value from the motor nameplate data. This data is used for calculating motor
torque, motor thermal protection etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating automatic
motor compensations.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide