3. Parameter Description
3.21.5. 23-8* Payback counter
The frequency converter includes a feature which can give a rough calculation on payback in cases where the frequency converter has been installed in
an existing plant to ensure energy saving by changing from fixed to variable speed control. Reference for the savings is a set value to represent the
average power yielded before the upgrade with variable speed control.
3
The difference between the Reference Power at fixed speed and the Actual Power yielded with speed control represent the actual saving.
As value for the fixed speed case, the rated motor size (kW) is multiplied with a factor (set in %) representing the power produced at fixed speed. The
difference between this reference power and the actual power is accumulated and stored. The difference in energy can be read in par. 23-83,
Savings
.
The accumulated value for the difference in power consumption is multiplied with the energy cost in local currency and the investment is subtracted. This
calculation for Cost Savings can also be read in par. 23-84,
{
Cost Savings
=
t
Actual Power Consumption
Break even (payback) occurs when the value read in the parameter turns from negative to positive.
It is not possible to reset the Energy Savings counter, but the counter can be stopped any time by setting par. 28-80,
Parameter overview:
Rated Motor Power
Power Reference Factor in %
Energy Cost per kWh
Investment
23-80 Power Reference Factor
Range:
*
100%
[0-100%]
200
t
(
Rated Motor Power
Power Reference Factor
= 0
Energy Cost
×
Parameter for settings
Par. 1-20
Par. 23-80
Par. 23-81
Par. 23-82
Function:
Set the percentage of the rated motor size (set in par. 1-20 or 1-21,
represent the average power yielded at the time running with fixed speed (before upgrade with variable speed
control).
Must be set to a value different from zero to start counting.
MG.11.C5.02 - VLT
Cost Savings
.
)
} −
Investment Cost
Energy Savings
Actual Power
Cost Savings
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
Power Reference Factor
Parameters for readout
Par. 23-83
Par. 16-10/11
Par. 23-84
Rated Motor Power
) which is supposed to
Energy
, to 0.