3. Parameter Description
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
3
[8]
NOT OR NOT
13-44 Logic Rule Boolean 3
Array [6]
3.13.6. 13-5* States
Parameters for programming the Smart Logic Controller.
13-51 SL Controller Event
Array [20]
13-52 SL Controller Action
Array [20]
*
Disabled
[0]
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset reference
0
[11]
Select preset reference
1
[12]
Select preset reference
2
[13]
Select preset reference
3
[14]
Select preset reference
4
[15]
Select preset reference
5
[16]
Select preset reference
6
122
Evaluates the expression [13-40/13-42] AND [13-44].
Evaluates the expression [13-40/13-42] OR [13-44].
Evaluates the expression [13-40/13-42] AND NOT [13-44].
Evaluates the expression [13-40/13-42] OR NOT [13-44].
evaluates the expression NOT [13-40/13-42] AND [13-44].
Evaluates the expression NOT [13-40/13-42] OR [13-44].
Evaluates the expression NOT [13-40/13-42] and evaluates AND NOT [13-44].
Evaluates the expression NOT [13-40/13-42] OR NOT [13-44].
Select the third boolean (TRUE or FALSE) input for the selected logic rule.
See Parameter 13-40 for further descriptions of choices and their functions.
Select the boolean input (TRUE or FALSE) to define the Smart Logic Controller event.
See Parameter 13-02 for further descriptions of choices and their functions.
Select the action corresponding to the SLC event. Actions are executed when the corresponding event (defined
in par. 13-51) is evaluated as true. The following actions are available for selection:
Changes the active set-up (par. 0-10) to '1'.
Changes the active set-up (par. 0-10) to '2'.
Changes the active set-up (par. 0-10) to '3'.
Changes the active set-up (par. 0-10) to '4'. If the set-up is changed, it will merge with other set-up commands
coming from either the digital inputs or via a fieldbus.
Selects preset reference 0.
Selects preset reference 1.
Selects preset reference 2.
Selects preset reference 3.
Selects preset reference 4.
Selects preset reference 5.
Selects preset reference 6.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide