Danfoss VLT FC 100 Series Programming Manual page 199

Hvac drive
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

®
VLT
HVAC Drive Programming Guide
NB!
The frequency converter has no back up of the clock function and the set date/time will reset to default (2000-01-01 00:00) after a
power down unless a Real Time Clock module with back up is installed. Consequently the logging will be stopped until date/time is
readjusted in par. 0-70,
set properly, e.g. after a power down.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-64 Timed Period Stop
Range:
*
2000-01-01 00:00
[2000-01-01
00:00 - 2099-12-31 23:59]
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-65 Minimum Bin Value
Range:
[0 - 100%]
23-66 Reset Continuous Bin Data
Option:
*
Do not reset
[0]
[1]
Do reset
23-67 Reset Timed Bin Data
Option:
*
Do not reset
[0]
[1]
Do reset
Date format will depend on setting in par. 0-71,
Format
.
Set Date and Time
Clock Fault
. In par. 0-79,
Function:
Set the date and time at which the Trend Analyses must stop update of the Timed Bin counters.
Date format will depend on setting in par. 0-71,
Format
.
Function:
Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between elements by
means of
and
buttons on the LCP.
Set the minimum limit for each interval in par. 23-61,
counter
Example: if selecting
[1] and changing setting from 10% to 12%,
counter
0 - <12% and
[1] on interval 12% - <20%.
Function:
Do reset
Select
[1] to reset all values in par. 23-61,
After pressing OK the setting of the parameter value will automatically change to
Function:
Do reset
Select
[1] to reset all counters in par. 23-62,
After pressing OK the setting of the parameter value will automatically change to
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3. Parameter Description
Date Format
, and time format on setting in par. 0-72,
, it is possible to program for a Warning in case clock not has been
Date Format
, and time format on setting in par. 0-72,
Continuous Bin Data
, and par. 23-62,
counter
[0] will be based on the interval
Continuous Bin Data
.
Timed Bin Data
.
Time
Time
Timed Bin Data
.
Do not reset
[0].
Do not reset
[0].
199
3