VLT
HVAC Drive Programming Guide
14-26 Trip Delay at Inverter Fault
Range:
*
5s
[0 - 35 s]
14-29 Service Code
Range:
*
-
[-2147483647 to +2147483647
N/A]
3.14.5. Current Limit Control, 14-3*
The frequency converter features an integral Current Limit Controller which is activated when the motor current, and thus the torque, is higher than the
torque limits set in par. 4-16 and 4-17.
When the current limit is reached during motor operation or regenerative operation, the frequency converter will try to reduce torque below the preset
torque limits as quickly as possible without losing control of the motor.
While the current control is active, the frequency converter can only be stopped by setting a digital input to
Any signal on terminals 18 to 33 will not be active until the frequency converter is no longer near the current limit.
Coast inverse
By using a digital input set to
is coasted.
14-30 Current Lim Cont, Proportional Gain
Range:
*
100 %
[0 - 500 %]
14-31 Current Lim Contr, Integration Time
Range:
*
0.020 s
[0.002 - 2.000 s]
3.14.6. Energy Optimising, 14-4*
Parameters for adjusting the energy optimisation level in both Variable Torque (VT) and Automatic Energy Optimization (AEO) mode.
Automatic Energy Optimization is only active if par.1-03, Torque Characteristics, is set for either
Optim. VT
[3].
14-40 VT Level
Range:
*
66%
[40 - 90%]
14-41 AEO Minimum Magnetisation
Range:
*
40%
[40 - 75%]
Function:
When the frequency converter detects an over-voltage in the set time trip will be effected after the set time.
Function:
Service use only.
Coast and reset inv.
[2] or
[3], the motor does not use the ramp-down time, since the frequency converter
Function:
Enter the proportional gain value for the current limit controller. Selection of a high value makes the controller
react faster. Too high a setting leads to controller instability.
Function:
Controls the current limit control integration time. Setting it to a lower value makes it react faster. A setting too
low leads to control instabillity.
Function:
Enter the level of motor magnetisation at low speed. Selection of a low value reduces energy loss in the motor,
but also reduces load capability.
This parameter cannot be adjusted while the motor is running.
Function:
Enter the minimum allowable magnetisation for AEO. Selection of a low value reduces energy loss in the motor,
but can also reduce resistance to sudden load changes.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3. Parameter Description
Coast inverse
[2] or
Coast and reset inv.
Auto Energy Optim. Compressor
[2] or
3
[3].
Auto Energy
129