3. Parameter Description
3.9.7. 8-7* BACnet
BACnet configuration
8-70 BACnet Device Instance
Range:
*
1
[0 - 4194304]
3
NB!
This parameter is active only when par. 8-30
8-72 MS/TP Max Masters
Range:
*
127
[0 - 127]
NB!
This parameter is active only when par. 8-30
8-73 MS/TP Max Info Frames
Range:
*
1
[1 - 65534]
NB!
This parameter is active only when par. 8-30
8-74 "I-Am" Service
Option:
*
Send at power-up
[0]
[1]
Continuously
NB!
This parameter is active only when par. 8-30
8-75 Initialisation Password
Range:
Size
*
related
[0 - 0]
96
Function:
Enter a unique ID number for the BACnet device.
Protocol
is set to [9]
Function:
Define the address of the master which holds the highest address in this network. Decreasing this value optimises
polling for the token.
Protocol
is set to [9]
Function:
Define how many info/data frames the device is allowed to send while holding the token.
Protocol
is set to [9]
Function:
Choose whether the device should send the "I-Am" service message only at power-up or continuously with an
interval of approx. 1 min.
Protocol
is set to [9]
Function:
Enter the password needed for execution of Drive Re-initialisation from BACnet.
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Programming Guide
FC Option
.
FC Option
.
FC Option
.
FC Option
.