3. Parameter Description
3.11.3. 10-1* DeviceNet
Parameters specific to the DeviceNet fieldbus.
10-10 Process Data Type Selection
Option:
3
[0]
Instance 100/150
[1]
Instance 101/151
[2]
Instance 20/70
[3]
Instance 21/71
10-11 Process Data Config Write
Option:
*
None
[0]
[3-02 ]
Minimum reference
[3-03 ]
Maximum reference
[3-41 ]
Ramp 1 ramp up time
[3-42 ]
Ramp 1 ramp down
time
[3-51 ]
Ramp 2 ramp up time
[3-52 ]
Ramp 2 ramp down
time
[3-80 ]
Jog ramp time
[3-81 ]
Quick stop ramp time
[4-11 ]
Motor speed low limit
(RPM)
[4-13 ]
Motor speed high limit
(RPM)
[4-16 ]
Torque
mode
[4-17 ]
Torque limit generator
mode
[5-90 ]
Digital & Relay Bus
Control
[5-93 ]
Pulse Out #27 Bus
Control
[5-95]
Pulse Out #29 Bus
Control
[6-53 ]
Terminal
Bus Control
108
Function:
Select the Instance (telegram) for data transmission. The Instances available are dependent upon the setting
of par. 8-10
Control Word Profile
When par. 8-10 is set to [0]
When par. 8-10 is set to [5]
Instances 100/150 and 101/151 are Danfoss-specific. Instances 20/70 and 21/71 are ODVA-specific AC Drive
profiles.
For guidelines in telegram selection, please refer to the DeviceNet Operating Instructions.
Note that a change to this parameter will be executed immediately.
Function:
Select the process write data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be
selected. Elements [0] and [1] of the array are fixed.
limit
motor
42
Output
MG.11.C5.02 - VLT
VLT
.
FC profile
, par. 10-10 options [0] and [1] are available.
ODVA
, par. 10-10 options [2] and [3] are available.
®
is a registered Danfoss trademark
®
HVAC Drive Programming Guide