Installing the MX960 Mounting Hardware for Center-Mounting in an
Open-Frame Rack
Before center-mounting the router in an open-frame rack, you must install the large mounting shelf on
the rack. The small mounting shelf is not needed.
Table 111 on page 260
specifies the holes in which you insert screws to install the mounting hardware in
an open-frame rack (an X indicates a mounting hole location). The hole distances are relative to one of the
standard U divisions on the rack. For reference, the bottom of all mounting shelves is at 0.04 in. (0.02 U)
above a U division.
Table 111: Mounting Hardware Hole Locations for Center-Mounting in an Open-Frame Rack
Hole
Distance Above U Division
30
17.26 in. (43.8 cm)
27
15.51 in. (39.4 cm)
24
13.76 in. (34.9 cm)
21
12.01 in. (30.5 cm)
18
10.26 in. (26.0 cm)
15
8.51 in. (21.6 cm)
12
6.76 in. (17.1 cm)
9
5.01 in. (12.7 cm)
6
3.26 in. (8.3 cm)
3
1.51 in. (3.8 cm)
2
0.88 in. (2.2 cm)
1
0.25 in. (0.6 cm)
Large Shelf
9.86 U
X
8.86 U
X
7.86 U
X
6.86 U
X
5.86 U
X
4.86 U
X
3.86 U
X
2.86 U
X
1.86 U
X
0.86 U
X
0.50 U
X
0.14 U
260