Each high-voltage second-generation universal power supply has a single feed. Input AC or DC receptacle
inlet is located on front panel of the power supply.
Each power cord feed must have dedicated circuit breakers. We recommend that size of the circuit breaker
protection should be designed according to National Electrical Code (NEC) of country of system installation
or any similar local standard based on maximum drawn current of the power supply specified in this guide.
RELATED DOCUMENTATION
MX960 AC Power Supply Description | 130
MX960 AC Power Electrical Safety Guidelines and Warnings
Replacing an MX960 AC Power Supply | 537

AC Power Cord Specifications for the MX960 Router

Each normal capacity AC power supply has a single AC appliance inlet located in the chassis directly above
the power supply that requires a dedicated AC power feed and each high-capacity AC PEM accepts two
AC feeds in two unique AC receptacles. Most sites distribute power through a main conduit that leads to
frame-mounted power distribution panels, one of which can be located at the top of the rack that houses
the router. An AC power cord connects each power supply to the power distribution panel.
You can order detachable AC power cords, each approximately 8 ft (2.5 m) long that supply AC power to
the router. The C19 appliance coupler at the female end of the cord inserts into the AC appliance inlet
coupler, type C20 (right angle) as described by International Electrotechnical Commission (IEC) standard
60320. The plug at the male end of the power cord fits into the power source receptacle that is standard
for your geographical location. If you want to use two AC feeds, two power cords are needed for each HC
AC power supply. For more information about AC power supplies, see
Description" on page
130.
The high-capacity second-generation AC power supply has two C20 receptacles on front panel of the
power supply. Make sure the power distribution cover is installed to cover C20 receptacles on PDM on
top of the chassis.
Table 96 on page 221
provides specifications and
cord provided for each country or region.
Table 96: AC Power Cord Specifications
Country
Australia
Figure 52 on page 222
Electrical Specification
240 VAC, 50 Hz AC
"MX960 AC Power Supply
depicts the plug on the AC power
Plug Type
SAA/3