The cache adapter card is only a separate failing item on migrated towers. If the cache adapter card is
located in a migrated tower, see the CACHE symbolic FRU in the Migrated Expansion Tower Problem
Analysis, Repair and Parts manual on the V5R1 Supplemental Manuals web site
instructions.

CAPPWR

For use by authorized service providers.
The Capacitor card (CAP) may be the failing item.
1. Is the SRC 1xx1-8468?
v No: Continue with the next step.
v Yes: Choose from the following options:
– If fewer than 3 DCAs are installed:
- If no capacitor card is installed in CAP 1 (M33) or CAP 2 (M37) location, install a card in CAP
1 location.
- If a capacitor card is present in either CAP 1 or CAP 2 location, reseat it. If the problem is not
fixed, replace it.
– If 3 or more DCAs are installed:
- If no capacitor card is installed in CAP 1 location, one is required.
- If a capacitor card is installed in either CAP 1 location, reseat it. If the problem is not fixed,
replace it.
2. For SRC 1xx1-8469:
v If no capacitor card is installed in CAP 2 (M37) location, install one. It is required.
v If a capacitor card is installed in CAP 2 location, reseat it. If the problem is not fixed, replace it.
v See Type, model, and part number list for the part number.
Note: Before replacing any field replaceable units (FRUs), verify that the card is seated correctly.
Table 1. CAPPWR for Models 870 and 890:
Unit Reference Code
1xx1- 8468
1xx1- 8469
This ends the procedure.

CBLALL

For use by authorized service providers.
A power cable may be the failing item.
When there is a location and part number displayed on the Control Panel of a system or expansion tower,
then you are to replace that FRU first.
Perform the following to determine the part number of the failing part.
1. Is the SRC 1xxx 2201 or 2301?
v No: Continue with the next step.
v Yes: The failing item is a power cable. Exchange the following parts one at a time.
– Base backplane power cable:
- PWR3A if installed - part 44H7809
- PWR3B if installed - part 44H7825
– Tape/Optical/Disk Unit power cable:
298
iSeries: iSeries Server 270, 800, 810, 820, 825, 830, 840, 870, 890, SB2, and SB3 Hardware Problem Analysis and
Isolation
CAP Unit/location
CAP-1/M33
CAP-2/M37
for FRU isolation