Yes: Exchange the following:
v
– AC module 1 and 2 (if installed)
– Concurrent maintenance adapter card A02
This ends the procedure.
6.
Exchange one of the following parts (see Locations for the model you are working on for part number
and remove and replace procedure information):
For FC 9074 or FC 9079 (single line cord) AC charger.
v
v
For FC 9074 or FC 9079 (dual line cord) AC Module. ("Power PIP11" on page 175 must be
performed before replacing parts.)
For Model 840/SB3 processor tower AC Module:
v
USA
World Trade 1PH
World Trade 2PH
If the problem is not resolved after exchanging the FRUs listed, exchange the tower card. See
symbolic FRU "TWRCARD" on page 470 if it was not previously exchanged.
This ends the procedure.
7.
Are you working on an FC 5033, FC 5034, FC 5035, or FC 5077 frame?
No: Continue with the next step.
v
Yes: Re-IPL the entire system to restore resources. If the reference code 00AC prevails after the
v
IPL, then return here and continue with the next step.
8.
The failing AC module is on a secondary expansion unit or base I/O unit. See Type, model, and part
number list for part numbers.
FC 5074 or FC 5079 (single line cord)
v
FC 5074 or FC 5079 (dual line cord) -"Power PIP11" on page 175 must be performed before
v
replacing parts.
Uninterruptible power supply base unit for FC 5033, FC 5034, or FC 5035
v
FC 5065 or FC 5066
v
AC Module FC 5071, FC 5073, FC 5077, FC 5081, or FC 5083
v
AC Module all other FC 5xxx
v
This ends the procedure.

AIRMOVR

For use by authorized service providers.
An air-moving device (AMD) may be failing. Before replacing any field replaceable units (FRUs), verify that
all cables are seated correctly.
Perform the following to determine the part number for the failing air-moving device. The address of the
failing frame and unit is shown in the second, third, and fourth characters of the four leftmost characters of
the system reference code (SRC). For example, 11-x xFFU-xxxx, where F=frame and U=unit.
1. Is the failing air moving device in a system unit?
v No: Go to step 2 (See page 273).
v Yes: Find the model and reference code in the following tables to determine the failing AMD. Then,
see Locations and addresses for the model you are working on to determine the location of the
failing item, information on the part number, and a link to the remove and replace procedure.
Table 1. For Model 270
Unit reference code
7610, 7611
FRU
AMD B01
Analyze hardware problems