Configure The Frequency Output - Emerson Micro Motion 9739 MVD Configuration And Use Manual

Hide thumbs Also See for Micro Motion 9739 MVD:
Table of Contents

Advertisement

Integrate the meter with the control system
June 2019
Postrequisites
CAUTION
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action to None. If you do not, the output will not report actual process data, and
this may result in measurement errors or unintended consequences for your process.
Options for mA Output Fault Action and mA Output Fault Level
Option
Upscale
Downscale (default)
Internal Zero
None

6.2 Configure the Frequency Output

The Frequency Output is used to report a process variable for mass or volume flow. Frequency Output does
not report density, temperature, or differential pressure. The Frequency Output parameters control how the
process variable is reported.
Important
Whenever you change a Frequency Output parameter, verify all other Frequency Output parameters before
returning the flowmeter to service. In some situations, the transmitter automatically loads a set of stored
values, and these values may not be appropriate for your application.
6.2.1 Configure Frequency Output Power Source
Display
OFF-LINE MAINT → OFF-LINE CONFG → IO → FO → POWER
Device Tools → Configuration → I/O → Channels
ProLink III
Field Communicator
Configure → Manual Setup → Inputs/Outputs → Frequency Output → FO Settings → Power Source
Use Frequency Output Power Source to set the power source for the Frequency Output. The power
configuration must match the wiring for the Frequency Output.
Procedure
Set Frequency Output Power Source as desired.
Option
Description
Internal
The output is powered by the transmitter.
80
mA Output behavior
Goes to the configured fault level
Goes to the configured fault level
Goes to the mA Output level associated with a
process variable value of 0 (zero), as determined
by Lower Range Value and Upper Range Value
settings
Tracks data for the assigned process variable; no
fault action
Configuration and Use Manual
MMI-20016855
mA Output Fault Level
Default: 22.0 mA
Range: 21.0 to 24.0 mA
Default: 2.0 mA
Range: 1.0 to 3.6 mA
Not applicable
Not applicable
Micro Motion 9739 MVD Transmitters