Integrate the meter with the control system
April 2019
Device Tools > Configuration > I/O > Outputs > mA Output x > Fault Action
ProLink III
Field Communicator
Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mAOxFault Settings > mAOx
Fault Action
mA Output Fault Action controls the behavior of the mA Output if the transmitter detects a fault condition.
Important
The fault action is implemented only if Alert Severity is set to Failure. If Alert Severity is set to any other
option, the fault action is not implemented.
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
Procedure
1. Set mA Output Fault Action as desired.
Default: Downscale
Important
If you set mA Output Fault Action to None, the mA Output will be controlled by the setting of Process
Variable Fault Action. In most cases, if you set mA Output Fault Action to None, you should also set
Process Variable Fault Action to None.
2. If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level to the signal
that the mA Output will produce during a fault.
Options for mAO Fault Action and mAO Fault Level
Option
Upscale
Downscale (default)
Internal Zero
None

8.3 Configure the Frequency Output

The Frequency Output is used to report current values of process variables. The frequency varies between
0 Hz and 14500 Hz in proportion to the current value of the assigned process variable.
Depending on your purchase order and channel configuration, your transmitter may have zero or one
Frequency Output. One channels is available to use as a Frequency Output:
Only Channel B can be configured as either Frequency Output 1 or Discrete Output 1.
102
mA Output behavior
Goes to the configured fault level
Goes to the configured fault level
Goes to the mA Output level associated with a
process variable value of 0 (zero), as determined
by Lower Range Value and Upper Range Value
settings
Determined by the setting of Process Variable
Fault Action
Configuration and Use Manual
MMI-20048166
mA Output Fault Level
Default: 22.0 mA
Range: 21.0 to 23.0 mA
Not applicable
Not applicable
Micro Motion 4200 Transmitters