Satec Expertmeter EM720 Operation Manual page 101

Power quality and revenue meter
Hide thumbs Also See for Expertmeter EM720:
Table of Contents

Advertisement

Chapter 5 Configuring the EM720
EM720 Power Quality and Revenue Meter
Monthly and Daily Billing Data Logs
Data log #15 is pre-configured for recording billing period
data. It keeps billing energy, maximum demand and
cumulative maximum demand for last 24 billing periods.
The file is updated at an end of billing period, normally
once a month.
Data log #16 is pre-configured for daily billing energy and
maximum demand recording for the last 120 days. It is
automatically updated once a day.
You cannot manipulate these files and may not reset them
unless you have special permissions.
See
Billing and Load Profile Log Files
file record structure.
Energy Load Profile Data Log
Data log #12 is pre-configured for recording energy load
profile data at 15-minute intervals. The file can keep data
for the last 120 days.
You cannot remove the file or change a file structure, but
you can still reset the file with an administration
password.
Periodic recording data to this file is triggered by Setpoint
#16 that is linked to the meter clock. To change the
periodic rate at which data is recorded, change the time
interval for the MINUTE INTERVAL trigger in Setpoint #16
(See
Using Control Setpoints
See
Billing and Load Profile Log Files
file record structure.
Configuring Recorders
in Appendix C for the
in Chapter 5).
in Appendix C for the
101

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Expertmeter EM720 and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Expertmeter em720t

Table of Contents