Power Quality and Revenue Meter EM720/EM720T Modbus Communications Protocol Reference Guide BG0457 Rev. A8...
Page 2
Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer is not responsible for any mistakes in printing or faulty instructions contained in this book. Notification of any errors or misprints will be received with appreciation.
Page 8
3.11 EN 50160:2007 Compliance Statistics Data Log..........121 3.12 EN 50160:2007 Harmonic Statistics Data Log.............126 3.13 EN 50160:2010 Compliance Statistics Data Log..........128 3.14 EN 50160:2010 Harmonic Statistics Data Log.............133 3.15 Billing/TOU Monthly Profile Data Log ..............137 3.16 Billing/TOU Daily Profile Data Log ..............139 3.17 Energy Load Profile Data Log ................140 4 DATA SCALES AND UNITS ..............
1 General This document specifies a subset of the Modbus communications protocol used to transfer data between a master computer station and the EM720. The document provides the complete information necessary to develop third-party communications software capable of communication with the EM720. Refer to the EM720 Installation Manual and EM720 Operation Manual for more information on communication connections and configuring communication parameters in your device.
Modbus protocol in the EM720. 2.1 Transmission Modes The EM720 can be set up to communicate on a serial Modbus network using either RTU, or ASCII serial transmission mode, and via the Internet using Modbus/TCP mode.
To map the EM720 register address to the range of the Modbus holding registers, add a value of 40001 to the EM720 register address. When a register address exceeds 9999, use a 6-digit addressing scheme by adding 400001 to the EM720 register address.
Current engineering scales (see Section 4): HI_ENG = Imax = CT primary current × 2 = 200.00 × 2 = 400.00A LO_ENG = 0A If the raw data reading is 250 then the current reading in engineering units will be as follows: Amps reading = 250 ×...
2.7 User Assignable Registers The EM720 has 120 user assignable registers in the address range of 0 to 119, any of which you can map to any register address accessible in the instrument. Registers that reside in different locations may be accessed by a single request by re-mapping them to adjacent addresses in the user assignable registers area.
The EM720 keeps a separate read pointer for each communication port so that access to the same file through a different port will not affect current active sessions for other ports.
Moreover, the EM720 takes all channel data for the currently accessed record to a separate buffer, so that even when the record is overwritten at the time of reading, you are still prevented from receiving partially updated data.
Page 16
Common File Transfer Log files can be read either in a sequence record-by-record, or in a random order. Each Read-File request fills the file response block with the data of the record pointed to by the file (or section) read pointer. If you want to begin reading a file from a particular record, which sequence number is known, you can change the pointer position by issuing the Set-File-Position request with the desired sequence number.
Page 17
1. If you wish to begin reading a file section from a particular record or from the first record, use either the Set-File-Position request with the desired record sequence number, or the Reset-File-Position request. Specify either a section number, or the channel ID for the section from where you want to read data.
2.10 TCP Notification Client The TCP notification client can establish connections with a remote Modbus/TCP server and send notification messages either on events, or periodically on a time basis. Notification messages are sent via a block of 24 Modbus registers using write function 16.
Page 19
Client connections are triggered via programmable setpoints. To send event notifications to a server, configure a setpoint to respond to desired triggers or to periodic time events and add the "Send notification" action to the end of the setpoint actions list. Setpoint operation events triggered by regular analog and digital triggers are reported twice - when the event starts and when it ends, except of the pulsed events and time triggers that will be reported once.
3.2 16-bit Scaled Analog Registers and Energy Counters - Basic Register Set Address Point ID Description Type Notes Low and High Scales Units 256-308 +0 0x1100 V1/V12 Voltage 0-Vmax UINT16 +1 0x1101 V2/V23 Voltage 0-Vmax UINT16 +2 0x1102 V3/V31 Voltage 0-Vmax UINT16 +3 0x1103...
Page 22
Address Point ID Description Type Notes Low and High Scales Units -kvarh net (high) 0-9999 ×1 Mvarh UINT16 5, 6 +39 0x1112 V1/V12 Voltage THD 0-999.9 0.1% UINT16 +40 0x1113 V2/V23 Voltage THD 0-999.9 0.1% UINT16 +41 0x1114 V3/V31 Voltage THD 0-999.9 0.1% UINT16...
3.3 16-bit Scaled Analog Registers, Binary Registers and Counters Address Point ID Description Type Notes Low and High Scales Units 3584 0x0000 None UINT16 3616 0x0080 Setpoint Status 0x0000-0xFFFF UINT16 Bitmap: 0=released, 1=operated 3648-3649 Special Inputs +0 0x0100 Not used UINT16 +1 0x0101 Phase rotation order...
Address Point ID Description Type Notes Low and High Scales Units +21 0x0B95 Current unbalance 0-300.0 0.1% UINT16 +22 0x0B96 Not used UINT16 +23 0x0B97 Not used UINT16 +24 0x0B98 Frequency (1-cycle) 0-100.00 0.01Hz UINT16 4352-4390 1-Cycle Phase Values +0 0x0C00 V1/V12 Voltage 0-Vmax UINT16...
Address Point ID Description Type Notes Low and High Scales Units +4 0x0D04 Low kVA 0-Pmax UINT16 +5 0x0D05 Low PF Lag 0-1.000 0.001 UINT16 +5 0x0D06 Low PF Lead 0-1.000 0.001 UINT16 +7 0x0D07 Low voltage THD 0-999.9 0.1% UINT16 2, 5 +8 0x0D08...
Address Point ID Description Type Notes Low and High Scales Units 4640-4655 Phasor +0 0x1080 V1/V12 Voltage magnitude 0-Vmax UINT16 +1 0x1081 V2/V23 Voltage magnitude 0-Vmax UINT16 +2 0x1082 V3/V31 Voltage magnitude 0-Vmax UINT16 +3 0x1083 Not used UINT16 +4 0x1084 I1 Current magnitude 0-Imax UINT16...
Address Point ID Description Type Notes Low and High Scales Units +15 0x128F Total PF -1.000-1.000 0.001 INT16 4800-4813 1-Second High Phase Values +0 0x1300 High voltage 0-Vmax UINT16 +1 0x1301 High current 0-Imax UINT16 +2 0x1302 High kW -Pmax-Pmax INT16 +3 0x1303 High kvar...
Address Point ID Description Type Notes Low and High Scales Units +5 0x1505 Battery DC voltage 0-9999.00 0.01V UINT16 +6 0x1506 Not used UINT16 +7 0x1507 Not used UINT16 +8 0x1508 V4x (neutral-ground) voltage 0-Vmax UINT16 Transient recorder Vn channel +9 0x1509 Internal temperature -200.0 to 200.0...
Address Point ID Description Type Notes Low and High Scales Units +6 0x2906 kW L1 -Pmax-Pmax INT16 +7 0x2907 kW L2 -Pmax-Pmax INT16 +8 0x2908 kW L3 -Pmax-Pmax INT16 +9 0x2909 kvar L1 -Pmax-Pmax INT16 +10 0x290A kvar L2 -Pmax-Pmax INT16 +11 0x290B kvar L3...
Address Point ID Description Type Notes Low and High Scales Units +18 0x2C12 V1/V12 Voltage THD 0-9999 0.1% UINT16 2, 5 +19 0x2C13 V2/V23 Voltage THD 0-9999 0.1% UINT16 2, 5 +20 0x2C14 V3/V31 Voltage THD 0-999.9 0.1% UINT16 2, 5 +21 0x2C15 I1 Current THD 0-999.9...
Address Point ID Description Type Notes Low and High Scales Units +14 0x340E kVA L3 0-Pmax UINT16 +15 0x340F Power factor L1 0-1.000 0.001 UINT16 Absolute value +16 0x3410 Power factor L2 0-1.000 0.001 UINT16 Absolute value +17 0x3411 Power factor L3 0-1.000 0.001 UINT16...
Address Point ID Description Type Notes Low and High Scales Units +10 0x370A Maximum kvar import sliding window demand 0-Pmax UINT16 +11 0x370B Maximum kVA sliding window demand 0-Pmax UINT16 +12 0x370C Not used UINT16 +13 0x370D Not used UINT16 +14 0x370E Not used UINT16...
Address Point ID Description Type Notes Low and High Scales Units … +7 0x4A87 Tariff #8 maximum demand 0-Pmax UINT16 8896-8903 Billing TOU Maximum Demand Register #7 +0 0x5300 Tariff #1 maximum demand 0-Pmax UINT16 +1 0x5301 Tariff #2 maximum demand 0-Pmax UINT16 …...
Address Point ID Description Type Notes Low and High Scales Units +1 0x6C81 V2 voltage 0-Vmax UINT16 +2 0x6C82 V3 voltage 0-Vmax UINT16 +3 0x6C83 Not used UINT16 +4 0x6C84 V12 voltage 0-Vmax UINT16 +5 0x6C85 V23 voltage 0-Vmax UINT16 +6 0x6C86 V31 voltage 0-Vmax...
Address Point ID Description Type Notes Low and High Scales Units +18 0x6D12 Zero-sequence current 0-Imax UINT16 +19 0x6D13 Not used UINT16 +20 0x6D14 Voltage unbalance 0-300.0 0.1% UINT16 +21 0x6D15 Current unbalance 0-300.0 0.1% UINT16 +22 0x6D16 Not used UINT16 +23 0x6D17 Not used...
Address Point ID Description Type Notes Low and High Scales Units +10 0x6E8A V3 interharmonics THD 0-999.9 0.1% UINT16 +11 0x6E8B Not used UINT16 +12 0x6E6E I1 interharmonics THD 0-999.9 0.1% UINT16 +13 0x6E8D I2 interharmonics THD 0-999.9 0.1% UINT16 +14 0x6E8E I3 interharmonics THD 0-999.9...
Page 43
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. For volts, amps, power and frequency scales and units refer to Section 4 ”Data Scales and Units”. For analog data scaling formulas and examples, see Section 2.6.1, “16-bit Scaled Integer Format”.
3.4 32-bit Analog Registers, Binary Registers and Counters Address Point ID Description Type Notes Options/Range Units 11776-11777 0x0000 None UINT32 11840 0x0080 Setpoint Status 0x00000000-0x0000FFFF UINT32 Bitmap: 0=released, 1=operated 11904-11907 Special Inputs +0,1 0x0100 Not used UINT32 +2,3 0x0101 Phase rotation order 0=error, 1=positive (ABC), UINT32 2=negative (CBA)
Address Point ID Description Type Notes Options/Range Units 0x0B01 Not used UINT32 0x0B02 Day of week 1-7, 1 = Sun, 7 = Sat UINT32 0x0B03 Year 0-99 UINT32 0x0B04 Month 1-12 UINT32 0x0B05 Day of month 1-31 UINT32 0x0B06 Hours 0-23 UINT32 0x0B07...
Address Point ID Description Type Notes Options/Range Units +6,7 0x0E03 High kvar -Pmax-Pmax INT32 +8,9 0x0E04 High kVA 0-Pmax UINT32 +10,11 0x0E05 High PF Lag 0-1000 ×0.001 UINT32 +12,13 0x0E06 High PF Lead 0-1000 ×0.001 UINT32 +14,15 0x0E07 High voltage THD 0-9999 ×0.1% UINT32...
Address Point ID Description Type Notes Options/Range Units +22,23 0x108B Not used INT32 +24,25 0x108C I1 Current angle -1800-1800 ×0.1º INT32 +26,27 0x108D I2 Current angle -1800-1800 ×0.1º INT32 +28,29 0x108E I3 Current angle -1800-1800 ×0.1º INT32 +30,31 0x108F I4 Current angle -1800-1800 ×0.1º...
Address Point ID Description Type Notes Options/Range Units +20,21 0x130A High current TDD 0-1000 ×0.1% UINT32 +22,23 0x130B High L-L voltage 0-Vmax UINT32 14336-14379 1-Second Total Values +0,1 0x1400 Total kW -Pmax-Pmax INT32 +2,3 0x1401 Total kvar -Pmax-Pmax INT32 +4,5 0x1402 Total kVA 0-Pmax UINT32...
Address Point ID Description Type Notes Options/Range Units +58,59 0x161D kvar export predicted sliding window demand 0-Pmax UINT32 +60,61 0x161E Not used UINT32 +62,63 0x161F Not used UINT32 +64,65 0x1620 Not used UINT32 +66,67 0x1621 I4 ampere demand 0-I4max UINT32 14720-14737 Instrumentation Total Energies +0,1 0x1700...
Address Point ID Description Type Notes Options/Range Units +28,29 0x340E kVA L3 0-Pmax UINT32 +30,31 0x340F Power factor L1 0-1000 ×0.001 UINT32 Absolute value +32,33 0x3410 Power factor L2 0-1000 ×0.001 UINT32 Absolute value +34,35 0x3411 Power factor L3 0-1000 ×0.001 UINT32 Absolute value...
Address Point ID Description Type Notes Options/Range Units +20,21 0x370A Maximum kvar import sliding window demand 0-Pmax UINT32 +22,23 0x370B Maximum kVA sliding window demand 0-Pmax UINT32 +24,25 0x3737 Not used UINT32 +26,27 0x370D Not used UINT32 +28,29 0x370E Not used UINT32 +30,31 0x370F Maximum kW export sliding window demand...
Address Point ID Description Type Notes Options/Range Units 21248-21299 Billing TOU Maximum Demand Register #3 +0,1 0x4A00 Tariff #1 maximum demand 0-Pmax UINT32 +2,3 0x4A01 Tariff #2 maximum demand 0-Pmax UINT32 … +14,15 0x4A07 Tariff #8 maximum demand 0-Pmax UINT32 +16-31 0x4A08- Reserved 0x4A0F...
Address Point ID Description Type Notes Options/Range Units +50,51 0x4A97 Tariff #8 cumulative maximum demand 0-999,999,999 UINT32 22400-22451 Billing TOU Maximum Demand Register #7 +0,1 0x5300 Tariff #1 maximum demand 0-Pmax UINT32 +2,3 0x5301 Tariff #2 maximum demand 0-Pmax UINT32 …...
Address Point ID Description Type Notes Options/Range Units +44, 45 0x6C96 Not used UINT32 +46, 47 0x6C97 Not used UINT32 +48, 49 0x6C98 Frequency 0-10000 ×0.01Hz UINT32 25728-25777 10-Minute RMS Values +0, 1 0x6D00 V1 voltage 0-Vmax UINT32 +2, 3 0x6D01 V2 voltage 0-Vmax UINT32...
Address Point ID Description Type Notes Options/Range Units +46,47 0x7817 Short voltage interruption, V2 residual voltage, %Un 0.01% UINT32 +48,49 0x7818 Short voltage interruption, V3 residual voltage, %Un 0.01% UINT32 +50,51 0x7819 Short voltage interruption, duration UINT32 +52,53 0x781A Voltage dip, V1 residual voltage, %Un 0.01% UINT32 +54,55 0x781B...
Minimum/Maximum Log Registers Address Point ID Description Type Notes Options/Range/Format Units 35840-35971 Minimum Phase Values +0,1 0x2C00 Min. V1/V12 Voltage 0-Vmax UINT32 +2,3 Timestamp UINT32 +4,5 0x2C01 Min. V2/V23 Voltage 0-Vmax UINT32 +6,7 Timestamp UINT32 +8,9 0x2C02 Min. V3/V31 Voltage 0-Vmax UINT32 +10,11...
Address Point ID Description Type Notes Options/Range/Format Units +78,79 Timestamp UINT32 +80,81 0x2C14 Min. V3/V31 Voltage THD 0-9999 ×0.1% UINT32 2, 4 +82,83 Timestamp UINT32 +84,85 0x2C15 Min. I1 Current THD 0-9999 ×0.1% UINT32 +86,87 Timestamp UINT32 +88,89 0x2C16 Min. I2 Current THD 0-9999 ×0.1% UINT32...
Address Point ID Description Type Notes Options/Range/Format Units +6,7 Timestamp UINT32 +8,9 0x2E02 Min. Frequency 0-Fmax ×0.01Hz UINT32 +10,11 Timestamp UINT32 +12,13 0x2E03 Min. Voltage unbalance 0-3000 ×0.1% UINT32 +14,15 Timestamp UINT32 +16,17 0x2E04 Min. Current unbalance 0-3000 ×0.1% UINT32 +18,19 Timestamp UINT32...
Address Point ID Description Type Notes Options/Range/Format Units 37376-37395 Maximum Auxiliary Values +0,1 0x3600 Max. I4 current 0-I4max UINT32 +2,3 Timestamp UINT32 +4,5 0x3601 Max. In Current 0-Imax UINT32 +6,7 Timestamp UINT32 +8,9 0x3602 Max. Frequency 0-Fmax ×0.01Hz UINT32 +10,11 Timestamp UINT32 +12,13...
Address Point ID Description Type Notes Options/Range/Format Units +48,49 0x3737 Not used UINT32 +50,51 Timestamp UINT32 +52,53 0x370D Not used UINT32 +54,55 Timestamp UINT32 +56,57 0x370E Not used UINT32 +58,59 Timestamp UINT32 +60,61 0x370F Maximum kW export sliding window demand 0-Pmax UINT32 +62,63...
3.6 Billing Period Data Address Point ID Description Options/Range Units Type Notes 40410 Billing period counter 0-99 UINT16 40411 Number of available billing periods UINT16 40412-41135 Present billing period data 41136-41859 Previous (most recent) billing period data 41860-42583 Second previous billing period data 42584-43307 Third previous billing period data 43308-44031...
Page 80
Address Point ID Description Options/Range Units Type Notes +66,67 0x4791 Register 2 total cumulative maximum demand 0-999,999,999 UINT32 +68,69 0x4792 Register 3 total cumulative maximum demand 0-999,999,999 UINT32 +70,71 0x4793 Register 4 total cumulative maximum demand 0-999,999,999 UINT32 +72,73 0x4794 Register 5 total cumulative maximum demand 0-999,999,999 UINT32...
Page 81
Address Point ID Description Options/Range Units Type Notes +150,151 0x4101 Register 5 tariff #2 energy 0-999,999,999 0.1 kWh UINT32 +152,153 0x4102 Register 5 tariff #3 energy 0-999,999,999 0.1 kWh UINT32 +154,155 0x4103 Register 5 tariff #4 energy 0-999,999,999 0.1 kWh UINT32 +156,157 0x4104 Register 5 tariff #5 energy...
Page 82
Address Point ID Description Options/Range Units Type Notes +236,237 0x4C04 Register 10 tariff #5 energy 0-999,999,999 0.1 kWh UINT32 +238,239 0x4C05 Register 10 tariff #6 energy 0-999,999,999 0.1 kWh UINT32 +240,241 0x4C06 Register 10 tariff #7 energy 0-999,999,999 0.1 kWh UINT32 +242,243 0x4C07 Register 10 tariff #8 energy...
Page 83
Address Point ID Description Options/Range Units Type Notes +320,221 0x4A03 Register 3 tariff #4 maximum demand 0-Pmax UINT32 +322,323 0x7704 Register 3 tariff #4 maximum demand timestamp UINT32 +324,325 0x4A04 Register 3 tariff #5 maximum demand 0-Pmax UINT32 +326,327 0x7705 Register 3 tariff #5 maximum demand timestamp UINT32 +328,329 0x4A05...
Page 84
Address Point ID Description Options/Range Units Type Notes +406,407 0x7701 Register 6 tariff #1 maximum demand timestamp UINT32 +408,409 0x4A81 Register 6 tariff #2 maximum demand 0-Pmax UINT32 +410,411 0x7702 Register 6 tariff #2 maximum demand timestamp UINT32 +412,413 0x4A82 Register 6 tariff #3 maximum demand 0-Pmax UINT32...
Page 85
Address Point ID Description Options/Range Units Type Notes +490,491 0x7786 Register 8 tariff #6 maximum demand timestamp UINT32 +492,493 0x5386 Register 8 tariff #7 maximum demand 0-Pmax UINT32 +494,495 0x7707 Register 8 tariff #7 maximum demand timestamp UINT32 +496,497 0x5387 Register 8 tariff #8 maximum demand 0-Pmax UINT32...
Page 86
Address Point ID Description Options/Range Units Type Notes +576,577 0x4816 Register 1 tariff #7 cumulative maximum demand 0-999,999,999 UINT32 +578,579 0x4817 Register 1 tariff #8 cumulative maximum demand 0-999,999,999 UINT32 +580,581 0x4910 Register 2 tariff #1 cumulative maximum demand 0-999,999,999 UINT32 +582,583 0x4911 Register 2 tariff #2 cumulative maximum demand...
Page 87
Address Point ID Description Options/Range Units Type Notes +660,661 0x5310 Register 7 tariff #1 cumulative maximum demand 0-999,999,999 UINT32 +662,663 0x5311 Register 7 tariff #2 cumulative maximum demand 0-999,999,999 UINT32 +664,665 0x5312 Register 7 tariff #3 cumulative maximum demand 0-999,999,999 UINT32 +666,667 0x5313 Register 7 tariff #4 cumulative maximum demand...
3.7 Device Control and Status Registers Address Point ID Description Options/Range Units Type Notes User Event Flags Registers (bitmap) 44032-44033 Event flags set register (0 = no effect, 1 = set) 0x00000000 - 0x000000FF UINT32 44034-44035 Event flags clear register (0=clear, 1 = no effect) 0x00000000 - 0x000000FF UINT32 44036-44037...
Address Point ID Description Options/Range Units Type Notes Write: 0=clear alarm, 1=no effect 44312-44325 Reserved Device Diagnostics Register 44326-44327 Device diagnostics. Nonvolatile register. UINT32 Bitmap Read: 0=no faults logged, 1= diagnostic failed at least once since last reset; Write: 0=clear diagnostic flag, 1=no effect.
Device Identification 46080-46111 +0,1 Device serial number 0-999999 UINT32 +2,3 Device model ID 72000 UINT32 +4-11 Device model name “EM720” CHAR16 Null-terminated string +12-13 Device options (bitmap) UINT32 +14-15 Device production date and time UINT32 +16-19 Not used UINT16 Device firmware version number...
Address Point ID Description Options/Range Units Type Notes +18-23 Reserved UINT16 Read as 65535 I maximum demand load current 0-20000 UINT16 I4 maximum demand load current 0-20000 UINT16 +26-31 Reserved UINT16 Read as 65535 Demands Setup 46240-46255 Power demand period (block interval) 1, 2, 3, 5, 10, 15, 30, 60 UINT16 Number of demand periods in a sliding window...
Address Point ID Description Options/Range Units Type Notes Energy LED pulse rate, Wh/impulse, varh/impulse (in 1-40 ×0.01Wh UINT16 secondary units) +9-15 Reserved UINT16 Read as 65535 Local Settings 46400-46415 Local time offset, min 0-+/-720 INT16 Daylight savings time (DST) option 0=DST disabled (standard time UINT16 only),...
Address Point ID Description Options/Range Units Type Notes +10,11 Delay between redials, sec 0-9999 UINT32 +12,13 Idle connection timeout, sec 0-9999, 0 = never UINT32 +14,15 Number of rings before answer 0-20, 0 = never answer UINT32 +16-23 Modem init string “AT&F&D1&C1”...
Address Point ID Description Options/Range Units Type Notes Ohm/km, Ohm/mile +26,27 Load-side power line length 0-10000000 0.001 UINT32 km/miles +28,29 Load-side power line resistance 0-100000 0.001 UINT32 Ohm/km, Ohm/mile +30,31 Load-side power line reactance 0-100000 0.001 UINT32 Ohm/km, Ohm/mile +32,33 Iron watt percent loss constant (%LWFe) 0-1000000 0.0001%...
Address Point ID Description Options/Range Units Type Notes SqNum UINT16 TrgOps UINT16 +62,63 IntgPd UINT32 Resv UINT16 +65-71 RCB name (logical_device/rcb_name) CTRL/rcb_name CHAR14 Reading register 71 advances to the MET1/rcb_name next RCB in the list Dataset references list (read) Dataset number UINT16 IEC 61850 Report Deadbands 49396-49426...
Address Point ID Description Options/Range Units Type Notes 51184-51189 Reserved DNP Events Setup 51190-51445 +0,1 Threshold/Deadband UINT32 A hysteresis for the point return 0 to 4.3×10 threshold is 0.05Hz for frequency and 2% of the operating threshold for other points DNP point number DNP point number available for the UINT16...
Address Point ID Description Options/Range Units Type Notes Pst period 1-10 UINT16 Not used UINT16 Harmonic Voltage THD, up to order 25-50 UINT16 Harmonics, up to order 25-40 UINT16 +14-15 Not used UINT16 Interharmonic Voltage Evaluation 0=disabled, 1=enabled UINT16 THD, up to order 25-50 UINT16 Interharmonics, up to order...
Address Point ID Description Options/Range Units Type Notes 2nd signaling frequency 1100-30000 ×0.1Hz UINT16 3rd signaling frequency 1100-30000 ×0.1Hz UINT16 4th signaling frequency 1100-30000 ×0.1Hz UINT16 Not used UINT16 Time Aggregation Voltage events aggregation interval 0-180 UINT16 +27-41 Not used UINT16 50880-50901 Reserved...
Address Point ID Description Options/Range Units Type Notes Data log parameter #13 ID 0x0000-0xFFFF UINT16 Data log parameter #14 ID 0x0000-0xFFFF UINT16 Data log parameter #15 ID 0x0000-0xFFFF UINT16 Data log parameter #16 ID 0x0000-0xFFFF UINT16 +16-31 Reserved UINT16 54006-54037 Data log #1 Setup 54038-54069 Data log #2 Setup...
Address Point ID Description Options/Range Units Type Notes 55670-55677 Daily profile #13: Season 4, Day type 1 55678-55685 Daily profile #14: Season 4, Day type 2 55686-55693 Daily profile #15: Season 4, Day type 3 55694-55701 Daily profile #16: Season 4, Day type 4 55702-55711 Reserved TOU Calendar Setup...
3.9 Expansion I/O Configuration Address Point ID Description Options/Range Units Type Notes I/O Slots Configuration Info 63008-63055 Module type See table below UINT16 +1-3 Not used UINT16 63008-63011 Slot 1 Configuration 63012-63015 Slot 2 Configuration 63016-63019 Slot 3 Configuration 63020-63055 Reserved I/O Type Info 63056-63119...
3.10 File Transfer Registers Address Point ID Description Options/Range Units Type Notes File Transfer Control Blocks 63120-63151 File Request Block File function 1 = ACK - acknowledgement UINT16 1 - clears the file transfer block 3 = set file position 3 - changes the file position 5 = reset file position 5 - sets the file position at the first...
NOTES: File sections for partitioned (multi-section) files, like Billing/TOU profile log files, can be requested either by a section number, or by a section channel ID. If a section number is set to 0xFFFF, the section channel ID will be used to identify the section. The section number will be returned in the response block. If a section number is written, then the corresponding channel ID will be returned in the file response block.
Address Point ID Description Options/Range Units Type Notes +24, 25 Not used µsec UINT32 +26, 27 Not used UINT32 +28, 29 Not used µsec UINT32 Maximum number of records 0-65535 UINT16 Number of parameters per data section record 0-16 UINT16 Section record size, bytes Byte UINT16...
Address Point ID Description Options/Range Units Type Notes Field 1 parameter ID 0-0×FFFF UINT16 Field 2 parameter ID 0-0×FFFF UINT16 … … Event Log Response Block 63152-63159 Block Heading Last file function 1, 3, 5, 11 UINT16 File ID UINT16 Section number UINT16 Section channel ID...
Address Point ID Description Options/Range Units Type Notes Trigger event number 0-65535 UINT16 +8, 9 Log value #1 INT32 +10, 11 Log value #2 INT32 … … 63160-… Record #1 (variable length) Record #16 (variable length) Waveform Log Response Block 63152-63159 Block Heading Last file function...
Address Point ID Description Options/Range Units Type Notes Last file function 1, 3, 5, 11 UINT16 File ID UINT16 Section number UINT16 Section channel ID UINT16 Number of records in the block 1–16 UINT16 Record size, words UINT16 Request variation UINT16 Not used UINT16...
Page 120
Address Point ID Description Options/Range Units Type Notes Current phase point ID (generic) 0-65535 UINT16 Volts phase point ID (generic) 0-65535 UINT16 +14, 15 Current reference (base), primary units See Generic Data in Section 3.4 INT32 +16, 17 Current magnitude, primary units See Generic Data in Section 3.4 INT32 +18, 19...
3.11 EN 50160:2007 Compliance Statistics Data Log File Record Point Label Point Type Notes Description Range Units Section Field No. Power Frequency 1 Nnv 0x5A00 Number of non-valid 10-sec intervals UINT32 0x5A01 Number of valid 10-sec intervals UINT32 3 N1 0x5A02 Number of incidents ±1%, N1 UINT32 4 N2...
Page 122
File Record Point Label Point Type Notes Description Range Units Section Field No. 6 V1 Plt Max 0x5B85 Maximum Plt on phase V1 0.01 UINT32 7 V2 N1 0x5B86 Number of incidents Plt > 1% on phase V2 UINT32 8 V2 Plt Max 0x5B87 Maximum Plt on phase V2 0.01 UINT32...
Page 123
File Record Point Label Point Type Notes Description Range Units Section Field No. 2 N2 180s 0x5D01 Number of polyphase incidents <180s UINT32 3 N3 >180s 0x5D02 Number of polyphase incidents >180s UINT32 4 V1 Min 0x5D03 Minimum residual voltage on phase V1 UINT32 5 V2 Min 0x5D04 Minimum residual voltage on phase V2...
Page 124
File Record Point Label Point Type Notes Description Range Units Section Field No. 15 V2 N5 300% 0x5E0E Number of incidents u>300% on phase V2 UINT32 16 V3 N1 120% 0x5E0F Number of incidents u>120% on phase V3 UINT32 17 V3 N2 150% 0x5E10 Number of incidents u>150% on phase V3 UINT32 18 V3 N3 200%...
Page 125
File Record Point Label Point Type Notes Description Range Units Section Field No. 3 N1 0x5F02 Number of polyphase harmonic voltage incidents, N1 UINT32 4 N2 0x5F03 Number of polyphase voltage THD incidents, N2 UINT32 5 N1/N, % 0x5F04 EN50160 harmonic voltage compliance ratio, N1/N 0.01% UINT32 6 N2/N, %...
File Record Point Label Point Type Notes Description Range Units Section Field No. Mains Signaling Voltage 1 Nnv 0x6000 Number of non-valid 3-sec intervals UINT32 0x6001 Number of valid 3-sec intervals UINT32 3 N1 0x6002 Number of polyphase incidents, N1 UINT32 4 N1/N, % 0x6003 EN50160 compliance ratio, N1/N...
Page 127
File Record Point Label Point Range Units Type Notes Description Section Field No. V2 Harmonic Voltage 1 THD MAX 0xC000 Maximum THD on phase 0.1% UINT32 2 THDO MAX 0xC001 Maximum odd harmonics THD 0.1% UINT32 3 THDE MAX 0xC002 Maximum even harmonics THD 0.1% UINT32...
3.13 EN 50160:2010 Compliance Statistics Data Log File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section Frequency Variation 1 Nnv 0xC080 Number of non-valid 10-sec intervals UINT32 0xC081 Number of valid 10-sec intervals UINT32 3 N1 0xC082 Number of values exceeded percentile limit...
Page 129
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 24 dU lim2 high 0xC117 High maximum limit of voltage variation, %Un 0.01% INT32 25 PercRank 0xC118 Compliance percentile rank, % 0.1% UINT32 Rapid Voltage Changes 1 N1 0xC180 Number of polyphase incidents...
Page 130
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 8 V2 THD max2 0xC307 Maximum THD on phase B/BC, % 0.1% UINT32 9 V3 N1 0xC308 Number of THD values exceeded percentile limit on phase C/CA UINT32 10 V3 THD max1 0xC309...
Page 131
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 35 PercRank 0xC3A2 Compliance percentile rank, % 0.1% UINT32 Voltage Interruptions (indicative statistics) 1 N1 0,5s 0xC880 Number of short polyphase interruptions <=500ms UINT32 2 N2 1s 0xC881 Number of short polyphase interruptions <=1s UINT32...
Page 132
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 29 dt max 40% 0xC91C Maximum duration of a polyphase dip < 40% UINT32 30 dt max 10% 0xC91D Maximum duration of a polyphase dip < 5% UINT32 31 V min 0.2s 0xC91E...
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 20 N42 400%/0,2ms 0xCA13 Number of polyphase impulses >400% and duration <=0.2 ms UINT32 21 N43 400%/0.5ms 0xCA14 Number of polyphase impulses >400% and duration <=0.5 ms UINT32 22 N44 400%/1ms 0xCA15...
Page 134
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section V3 Harmonic Compliance UINT32 1 Nnv 0xCD00 Number of non-valid 10-min intervals UINT32 0xCD01 Number of valid 10-min intervals UINT32 3 H02 N1 0xCD02 Number of H02 values exceeded percentile limit on phase C/CA UINT32 4 H03 N1 0xCD03...
Page 135
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 41 H40 N1 0xCD28 Number of H40 values exceeded percentile limit on phase A/AB UINT32 42 PercRank 0xCD29 Compliance percentile rank, % 0.1% UINT32 V2 Interharmonic Compliance UINT32 1 Nnv 0xCD00...
Page 136
File Record Point Label Point ID Range Units Type Notes Description Channel/ Field No. Section 40 %H02 max2 0xCCA7 Maximum value of H02 on phase C/CA, % 0.01% UINT32 41 %H03 max2 0xCCA8 Maximum value of H03 on phase C/CA, % 0.01% UINT32 …...
3.15 Billing/TOU Monthly Profile Data Log File Record Point Label Point Description Range Type Notes Units Channel/ Field No. Section Energy Register #1 1 REG1 0x1780 Summary (total) energy reading 0-999,999,999 0.1 kWh UINT32 2 TRF1 0x7000 Tariff #1 energy reading 0-999,999,999 0.1 kWh UINT32...
Page 138
File Record Point Label Point Description Range Type Notes Units Channel/ Field No. Section 17 TIME5 0x7705 Tariff #5 maximum demand timestamp UINT32 18 TRF5 CMD 0x7184 Tariff #5 cumulative maximum demand 0-999,999,999 UINT32 19 TRF6 MD 0x7105 Tariff #6 maximum demand 0-Pmax UINT32 20 TIME6...
An energy use profile section is allocated for registers for which a source input is selected in the Energy/TOU Register setup and for which energy use profile is enabled. A maximum demand profile section is allocated for registers for which maximum demand profile is enabled in the Energy/TOU Register setup. Not configured sections/channels are not available for download. Refer to the file channel mask in the file info for configured channels.
4 Data Scales and Units Code Condition Value Range Notes Data Scales Vmax Voltage scale × PT Ratio, V Imax Current Scale × CT Ratio I4max Current Scale × I4 CT Ratio Pmax Vmax × Imax × 2, W Fmax 100 Hz AImin +/-1mA...
5 Data Formats Format Code Value Description Notes Timestamp Local time in a UNIX-style format. Represents the number of seconds since midnight (00:00:00), January 1, 1970. The time is valid after January 1, 2000. File ID Event log Data log #1-8 Data log #9 –...
Format Code Value Description Notes Event Cause/Point ID Setpoint Operation Events 0x0000-0x59FF Trigger parameter ID 0x6400-0xFFFF Trigger parameter ID Setpoint Action Events 0x5A00-0x5A0F Setpoint #1-#16 Communications Events 0x5B00-0x5BFF Point ID (low byte, see F21) Front Panel Operations 0x5C00-0x5CFF Point ID (low byte, see F21) Self-Check Diagnostics Events 0x5D00-0x5DFF Point ID (low byte, see F21)
Format Code Value Description Notes 0xF600 Enabled 0xF700 Disabled 0xF800 Started 0xF801 Begin 0xF900 Stopped 0xF901 Setpoint Operation Events 0xE100-0xE10F Setpoint operated (low byte = setpoint ID) 0xE200-0xE20F Setpoint released (low byte = setpoint ID) Setpoint Action Events See F14 Setpoint action ID Data Point ID Data Locations...
Format Code Value Description Notes Single-Bit Binary Input Binary Input With Status Binary Input Change Event Objects Binary Input Change Without Time Binary Input Change With Time Static Binary Counters 32-bit Binary Counter 32-bit Binary Counter Without Flag 16-bit Binary Counter 16-bit Binary Counter Without Flag Binary Counter Change Events 32-bit Counter Change Event Without Time...
Format Code Value Description Notes 16:19 PQ option (user-selectable): V26.XX.20 and later 2 = EN 50160:2007 5 = EN 50160:2010 20:31 Not used IEC 61850 Measured Value Indices Phase voltage Not used Not used Phase currents Neutral current Auxiliary current I4 Not used Not used Not used...