Chapter 5 Configuring the EM720
Configuring the Season Tariff and DST Schedule
EM720 Power Quality and Revenue Meter
2. Select the start time for each tariff change point
and the corresponding active tariff number.
3.
Repeat the setup for all active profiles.
The first tariff change point is fixed at 00:00 hours, and
the last tariff change you specified will be in use until
00:00 hours on the next day.
NOTE
The billing monthly and daily profile files, and your billing
data display are automatically configured for the number
of active tariffs you defined in the meter TOU daily profile.
The EM720 TOU calendar provides a season tariff schedule
and an option for scheduled daylight savings switch dates.
To
configure
your
Energy/TOU from the Meter Setup menu, and then click on
the TOU Calendar tab.
The meter TOU calendar allows you to configure any tariff
schedule based on any possible utility regulation. The
calendar provides 48 entries that allow you to specify
profiles for working days and holidays through all seasons
in any order that is convenient for you, based on simple
intuitive rules. There are no limitations on how to define
your schedule. The meter is able to automatically
Configuring Billing/TOU
season
tariff
schedule,
select
91