Viewing En50160 Statistics Reports; Viewing The En50160 Compliance Report - Satec Expertmeter EM720 Operation Manual

Power quality and revenue meter
Hide thumbs Also See for Expertmeter EM720:
Table of Contents

Advertisement

Chapter 9 Viewing Log Files and Reports

Viewing EN50160 Statistics Reports

Viewing the EN50160 Compliance Report

152
To get the EN50160 Compliance report, select "EN50160
Compliance Statistics" from the Reports menu, point to
the database where you stored the retrieved statistics
data, uncheck the voltage characteristics' tables you do
not want to be reported, and then click Open.
An example of the EN50160 compliance report is shown in
the following picture.
The standard compliance statistics is reported within the
selected time range on a daily, weekly or yearly basis
depending on the observation periods stated in the
EN50160 for voltage characteristics. If the time range
includes a number of the observation intervals, each
interval's statistics is given in a separate row. For power
frequency, both weekly and yearly compliance statistics
are provided.
For characteristics provided with definite limits, the report
shows a percentage of the observation time within which
the characteristic complied with the standard, e.g. 98% of
the observations in a period of one week, and the total
compliance indicator.
For voltage characteristics provided with indicative values,
the report gives the yearly statistical data classified by
voltage magnitude and duration.