Communication PROFIBUS DP/PROFINET IO
10.1 Communication according to PROFIdrive
Display parameters drive
● r0481[0...2] CO: Encoder status word Gn_ZSW
● r0482[0...2] CO: Encoder position actual value Gn_XIST1
● r0483[0...2] CO: Encoder position actual value Gn_XIST2
● r0487[0...2] CO: Diagnostic encoder control word Gn_STW
10.1.3.5

Central control and status words

Description
The central process data exists for different telegrams. For example, telegram 391 is used
for transferring measuring times and digital inputs/outputs.
The following central process data are available:
Receive signals:
● CU_STW1 Control Unit control word
● A_DIGITAL digital outputs
● MT_STW probe control word
Transmit signals:
● CU_ZSW1 Control Unit status word
● E_DIGITAL digital inputs
● MT_ZSW Probe status word
● MTn_ZS_F Probe n measuring time, falling edge (n = 1-6)
● MTn_ZS_S Probe n measuring time, rising edge (n = 1-6)
CU_STW1 (control word for Control Unit, CU)
See function diagram [2495].
Table 10- 34 Description of CU_STW1 (control word for Control Unit)
Bit
Meaning
0
Synchronization flag
1
RTC PING
2...6
Reserved
7
Acknowledging faults
8...9
Reserved
462
This signal is used to synchronize the joint system time between the
controller and drive unit.
This signal is used to set the UTC time using the PING event.
0/1
Acknowledging faults
-
-
Remarks
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
BICO
BI: p0681[0]
BI: p3104
BI: p2103
-
Drive functions