Current Setpoint Filter; Current Controller Adaptation - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.10

Current setpoint filter

Description
The two current setpoint filters connected in series can be parameterized as follows:
● Low-pass 2nd order (PT2): -40 dB/decade)
● General 2nd-order filter
Function diagrams (see SINAMICS S120/S150 List Manual)
● 6710 Current setpoint filters
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p1655 CI: Current setpoint filter natural frequency tuning
● ...
● p1666 Current setpoint filter 2 numerator damping
4.11

Current controller adaptation

Description
Current controller adaptation can be used to adapt the P gain of the current controller and
the dynamic pre-control of the Iq current controller depending on the current. The current
controller adaptation is directly activated with setting p1402.2 = 1 or deactivated with
p1402.2 = 0. It is automatically activated with p1959.5 (p1959.5 = 1) or deactivated (p1959.5
= 0).
Figure 4-17
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
STARTER converts band-stop and low-pass with reduction in the parameters of the
general 2nd order filter.
– Bandstop
– Low-pass with reduction by a constant value
The phase frequency curve is shown alongside the amplitude log frequency curve. A
phase shift results in a control system delay and should be kept to a minimum.
Current controller adaptation for p0393 < 1, with p0391 < p0392
Vector control
4.10 Current setpoint filter
145

Advertisement

Table of Contents
loading

Table of Contents