Automatic Restart (Vector, Servo, Infeed) - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Basic functions

6.8 Automatic restart (vector, servo, infeed)

6.8
Automatic restart (vector, servo, infeed)
Description
The automatic restart function is used to automatically restart the drive/drive group when the
power is restored after a power failure. In this case, all of the faults present are automatically
acknowledged and the drive is powered-up again. This function is not only restricted to line
supply faults; it can also be used to automatically acknowledge faults and to restart the
motor after any fault trips. In order to allow the drive to be powered-up while the motor shaft
is still rotating, the "flying restart" function should be activated using p1200.
CAUTION
Automatic restart functions in the vector, servo mode and for infeeds with closed-loop
infeed control. After the line supply voltage is connected, Smart Line Modules 5kW/10kW
automatically power themselves up.
If p1210 is set to the value > 1, the Line Modules / motors can start automatically once the
line supply has been re-established. This is especially critical, if, after longer line supply
failures, motors come to a standstill (zero speed) and it is incorrectly assumed that they
have been powered-down. For this reason, entering the area around the drive when it is in
this condition can cause death, serious injury, or considerable material damage.
Automatic restart mode
Table 6- 6
0
1
208
WARNING
Automatic restart mode
p1210
Mode
Disables automatic restart
Acknowledges all faults without
restarting
Meaning
Automatic restart inactive
When p1210 = 1, faults that are present are
acknowledged automatically when their cause is
rectified. If further faults occur after faults have been
acknowledged, then these are also again
automatically acknowledged. A minimum time of
p1212 + 1s must expire between successful fault
acknowledgement and a fault re-occurring if the
signal ON/OFF1 (control word 1, bit 0) is at a HIGH
signal level. If the ON/OFF1 signal is at a LOW
signal level, the time between a successful fault
acknowledgement and a new fault must be at least
1s.
For p1210 = 1, fault F07320 is not generated if the
acknowledge attempt failed (e.g. because the faults
occurred too frequently).
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Drive functions

Advertisement

Table of Contents
loading

Table of Contents