Basic functions
6.9 Armature short-circuit brake, internal voltage protection, DC brake
External armature short-circuit braking
The external armature short-circuit is activated via p1231 = 1 (with contactor feedback
signal) or p1231 = 2 (without contactor feedback signal). It is initiated when the pulses are
canceled.
This function controls an external contactor via output terminals, which then short-circuits the
motor through resistors when the pulses are canceled. Armature short-circuit braking has the
advantage with respect to a mechanical brake that at the start of braking (at a high speed),
the braking effect is initially high. However, at lower speeds, the braking effect is significantly
decreases - this is the reason that we recommend a combination with a mechanical brake.
A prerequisite for the use of the external armature short-circuit is:
● One of the following motor types was parameterized:
In case of incorrect parameterization (e.g. induction motor and external armature short-circuit
selected), a fault message 7906 "Armature short-circuit / DC brake parameterization error" is
generated.
r0046.4
p1230
(0)
(r0046.19 = 1)
r0046.20
Figure 6-3
External armature short-circuit braking with/without contactor feedback signal
Integrated voltage protection (booksize)
For detailed information about integrated voltage protection, please refer to chapter
"Integrated voltage protection".
212
– Rotating permanent-magnet synchronous motor (p0300 = 2xx)
– Linear permanent-magnet synchronous motor (p0300 = 4xx)
p1231 = 1
1
p1235
r0002 = 19
≥1
r1239.0
p1236 =
T
=1
p1237 = 200
0
1
DI
DO
200
ms
0
&
&
ms
T
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
+24 V
M
~
3
F07905
A07904
2000
µs
p1231 = 1
p1231 = 2
Drive functions