2.4

Fixed speed setpoints

Description
This function can be used to specify preset speed setpoints. The fixed setpoints are defined
in parameters and selected via binector inputs. Both the individual fixed setpoints and the
effective fixed setpoint are available for further interconnection via a connector output (e.g. to
connector input p1070 - CI: main setpoint).
Properties
● Number of fixed setpoints: Fixed setpoint 1 to 15
● Selection of fixed setpoints: Binector input bits 0 to 3
Function diagrams (see SINAMICS S120/S150 List Manual)
● 1550 Overviews - setpoint channel
● 3010 Fixed speed setpoints
Overview of important parameters (see SINAMICS S120/S150 List Manual)
Adjustable parameters
● p1001[D] CO: Fixed speed setpoint 1
● ...
● p1015[D] CO: Fixed speed setpoint 15
● p1020[C] BI: Fixed speed setpoint selection Bit 0
● p1021[C] BI: Fixed speed setpoint selection Bit 1
● p1022[C] BI: Fixed speed setpoint selection Bit 2
● p1023[C] BI: Fixed speed setpoint selection Bit 3
Display parameters
● r1024 CO: Fixed speed setpoint effective
● r1197 Fixed speed setpoint current number
Parameterization with STARTER
In the STARTER commissioning tool, the "Fixed setpoints" parameter screen in the project
navigator under the relevant drive is activated by double-clicking Setpoint channel -> Fixed
setpoints.
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
– Binector input bits 0, 1, 2 and 3 = 0 -> setpoint = 0 active
– Unused binector inputs have the same effect as a "0" signal
Extended setpoint channel
2.4 Fixed speed setpoints
51