Note
The factory settings are "ON" or "OFF" for all switches. With these two settings, the
PROFIBUS address is set by parameterization.
Parameter p0918 is unique to the Control Unit (see Control Unit). The factory setting is 126.
Address 126 is used for commissioning. Permitted PROFIBUS addresses are 1 ... 126.
If more than one CU is connected to a PROFIBUS line, the address settings must differ from
the factory settings. Note that each address can only be assigned once on a PROFIBUS
line. This can be achieved using the address switch or by setting parameter p0918
accordingly. The setting can be made by connecting the 24 V supply step by step and
resetting p0918, for example.
The address setting on the switch is displayed in r2057.
Each change made to the bus address is not effective until POWER ON.
Device master file
A device master file provides a full and clear description of the features of a PROFIBUS
slave.
The GSD files can be found at the following locations:
● On the Internet: http://www4.ad.siemens.de/WW/view/de/113204
● On the CD for the STARTER commissioning tool
● On the memory card in directory
Note for commissioning for VIK–NAMUR
To be able to operate a SINAMICS drive as a VIK-NAMUR drive, standard telegram 20 must
be set and the VIK-NAMUR identification number activated via p2042 =1.
Device identification
An identification parameter for individual slaves facilitates diagnostics and provides an
overview of the nodes on the PROFIBUS.
The information for each slave is stored in the following CU-specific parameter:
r0964[0...6] device identification
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Order no. 6SL3072-0AA00-0AGx
\\SIEMENS\SINAMICS\DATA\CFG\
Communication PROFIBUS DP/PROFINET IO
10.2 Communication via PROFIBUS DP
493