Reactive current control

A reactive current setpoint can be set to compensate the reactive current or to stabilize the
line voltage in infeed mode. The total setpoint is the sum of the fixed setpoint p3610 and the
dynamic setpoint via the connector input p3611.
Note
The direction of rotation of the network is compensated automatically with reactive current
control. A negative reactive current setpoint causes an inductive reactive current; a positive
setpoint generates a capacitive reactive current.
Note
The closed-loop control limits the reactive current setpoint dynamically in such a way that the
sum of the active current setpoint and the reactive current setpoint does not exceed the
maximum device current.
Note
The reactive current consumption of the line filter selected in the configuration Wizard is
automatically covered by the Active Infeed closed-loop control. This means that the display
value of the current reactive current setpoint in r0075 no longer corresponds with the
parameterized total reactive current setpoint.
Note
The reactive power setpoint of the Line Module with respect to the network can be derived
by multiplying the parameterized total reactive current setpoint by 1.73 * rated line voltage.
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Internal status
Parameter
word
ZSWAE.7
r2139.7
ZSWAE.9
r0899.9
ZSWAE.11
r0899.11
ZSWAE.12
r0899.12
1.1 Active Infeed
PROFIdrive telegram 370
A_ZSW1.7
A_ZSW1.9
A_ZSW1.11
A_ZSW1.12
Infeed
29

Advertisement

Table of Contents
loading

Table of Contents