In the following cases, when a DDS switch takes place, the current actual position value
becomes invalid (p2521 = 0) and the reference point (r2684.11 = 0) is reset.
● The EDS that is effective for the position control changes.
● The encoder assignment changes (p2502).
● The mechanical relationships change (p2503...p2506)
With absolute encoders, the status of the adjustment (p2507) is also reset, if the same
absolute encoder is selected for the position control although the mechanical relationships
have changed (p2503 ... p2506).
In operating mode, a fault message (F07494) is also generated.
The following table contains a few examples for data set switching. The initial data set is
always DDS0.
Table 7- 6
DDS switchover without load gear position tracking
DDS p186
p187
(MDS)
(encoder_1)
0
0
EDS0
1
0
EDS0
2
0
EDS0
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
p188
p189
(encoder_2)
(encoder_3)
EDS1
EDS2
EDS1
EDS2
EDS1
EDS2
Encoder
Mechanic
Load gear
for
al
position
position
condition
tracking
control
s
p2502
p2504/
p2505/
p2506 or
p2503
encoder_
xxx
disabled
1
encoder_
xxx
disabled
1
encoder_
yyy
disabled
1
Function modules
7.9 Basic positioner
Switchover response
---
Switchover during pulse
inhibit or operation has no
effect
Pulse inhibit: Position
actual value conditioning is
newly initiated
and
1)
reference bit
is reset.
2)
Operation:
Fault message is
generated. Position actual
value conditioning is newly
initiated
and reference bit
1)
is reset.
2)
301