Communication PROFIBUS DP/PROFINET IO
10.1 Communication according to PROFIdrive
Bit
3.....
...15
MDI_MODE
This process data defines the mode for MDI sets.
Precondition: p2654 > 0
MDI_MODE = xx0x hex –> Absolute
MDI_MODE = xx1x hex –> Relative
MDI_MODE = xx2x hex –> Abs_pos (with modulo offset only)
MDI_MODE = xx3x hex –> Abs_neg (with modulo offset only)
E_STW1 (control word for infeeds)
See function diagram [2447].
Table 10- 15 Description of E_STW1 (control word for infeeds)
Bit
Meaning
0
ON/OFF1
1
OFF2
Note:
Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
2
Reserved
3
Enable operation
4
Reserved
5
Inhibit motor operation
Note:
When "Inhibit motoring operation" is present, power can still be drawn from the DC link. The DC link voltage is then
no longer controlled. The voltage level is the same as the rectified value of the current line voltage.
432
Meaning
Reserved
0/1
0
1
0
-
1
0
-
1
0
-
-
Remarks
ON
Pulse enable possible
OFF1
Reduce DC link voltage via ramp (p3566),
followed by pulse inhibit/line contactor open
No OFF2
Enable possible
OFF2
Immediate pulse suppression and switching on
inhibited
-
Enable operation
Pulse enable is present
Disable operation
Pulse inhibit is present
-
Inhibit motor operation
Motoring operation as step-up converter is
inhibited.
Enable motor operation
Motoring operation as step-up converter is
enabled.
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Interconnection
parameter
-
-
BICO
BI: p0840
BI: p0844
-
BI: p0852
-
BI: p3532
Drive functions