Basic information about the drive system
12.6 Parameterizing using the BOP20 (Basic Operator Panel 20)
Name
Unplug while voltage is
present
Actuating keys
Overview of important parameters (refer to the SINAMICS S120/S150 List Manual)
All drive objects
● p0005 BOP operating display selection
● p0006 BOP operating display mode
● p0013 BOP user-defined list
● p0971 Drive object, save parameters
Drive object, Control Unit
● r0002 Control Unit status display
● p0003 BOP access level
● p0004 BOP display filter
● p0007 BOP background lighting
● p0008 BOP drive object selection
● p0009 Device commissioning, parameter filter
● p0011 BOP password input (p0013)
● p0012 BOP password confirmation (p0013)
● r0019 CO/BO: Control word, BOP
● p0977 Save all parameters
Other drive objects (e.g. SERVO, VEKTOR, INFEED, TM41 etc.)
● p0010 Commissioning parameter filter
590
The BOP can be withdrawn and inserted under voltage.
The ON and OFF keys have a function.
When withdrawing, the drives are stopped.
Once the BOP has been inserted, the drives must be switched on again.
.
ON and OFF keys have no function
Withdrawing and inserting has no effect on the drives.
The following applies to the "P" and "FN" keys:
When used in a combination with another key, "P" or "FN" must be pressed first and then
the other key.
Description
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5