Basic information about the drive system
12.4 BICO technology: interconnecting signals
Note
A connector input (CI) cannot be interconnected with any connector output (CO, signal
source). The same applies to the binector input (BI) and binector output (BO).
For each CI and BI parameter, the parameter list shows under "data type" the information
on the data type of the parameter and the data type of the BICO parameter.
For CO parameters and BO parameters, only the data type of the BICO parameter is
shown.
Notation:
Data types BICO input: Data type parameter / Data type BICO parameter
Example: Unsigned32 / Integer16
Data types BICO output: Data type BICO parameter
Example: FloatingPoint32
The possible interconnections between the BICO input (signal sink) and the BICO output
(signal source) are listed in the following documents:
References: SINAMICS S120/S150 List Manual,
interconnections".
The BICO parameter interconnection can be implemented in different command data sets
(CDS). The different interconnections are activated by switching data sets. Interconnections
across drive objects are also possible.
12.4.4

Internal encoding of the binector/connector output parameters

The internal codes are required for writing BICO input parameters via PROFIBUS, for
example.
Figure 12-6
576
section "Explanation of list of parameters" in table "Possible combinations for BICO
Internal encoding of the binector/connector output parameters
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Drive functions