Siemens SINAMICS S120 Function Manual page 450

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Communication PROFIBUS DP/PROFINET IO
10.1 Communication according to PROFIdrive
FAULT_CODE
Display of the fault code (see function diagram 8060).
E_ZSW1 (status word for infeed)
See function diagram [2457].
Table 10- 29 Description of E_ZSW1 (status word for infeed)
Bit
Meaning
0
Ready for switching on
1
Ready for operation
2
Operation enabled
3
Fault active
4
No OFF2 active
5
Reserved
6
Switching on inhibited
7
Reserved
8
Reserved
9
Control request to PLC
10
Reserved
11
Bypass energized
12
Line contactor activated
13...1
Reserved
5
450
Remarks
1
Ready for switching on
0
Not ready for switching on
1
Ready for operation
DC link pre-charged, pulses inhibited
0
Not ready for operation
1
Operation enabled
Vdc = Vdc_setp
0
Operation inhibited
1
Fault active
0
No fault
1
No OFF2 active
0
OFF2 active
1
Switching on inhibited
Fault active
0
No "switching on inhibited" active
1
Control requested
The PLC is requested to assume control. Condition
for applications with isochronous mode: drive
synchronized with PLC system.
0
Local operation
Control only possible on device
1
Bypass energized
Pre-charging is complete and the bypass relay for
the pre-charging resistors is energized.
0
Bypass not energized
Pre-charging not yet complete.
1
Line contactor activated
0
Line contactor not energized
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
BICO
BO: r0899.0
BO: r0899.1
BO: r0899.2
BO: r2139.3
BO: r0899.4
BO: r0899.6
BO: r0899.9
BO: r0899.11
BO: r0899.12
Drive functions