Figure 11-4
Example: Hot plugging
Using the hot-plugging function, components can be withdrawn from the operational drive
line-up (the other components continue to operate) on the DRIVE-CLiQ line. This means that
the corresponding drive object must first be deactivated/parked beforehand using parameter
p0105 or STW2.7.
The following requirements must be satisfied:
Hot plugging is only possible when a drive object is connected in a star configuration to a
Control Unit or to the DRIVE-CLiQ Hub DMC20.
The system does not support removing DRIVE-CLiQ connections between the other DRIVE-
CLiQ components e.g. Sensor/Terminal Module to Motor Module, Motor Module to Motor
Module.
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Example, distributed topology using DMC20
11.4 Application examples with the DMC20
Applications
545