Communication PROFIBUS DP/PROFINET IO
10.2 Communication via PROFIBUS DP
● PROFIBUS interface
● PROFIBUS diagnostic LED
Note
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnostics purposes.
Setting the PROFIBUS address
Two methods are available for setting the PROFIBUS address:
1. Via the PROFIBUS address switches on the Control Unit
2. Via p0918
Example:
Setting the PROFIBUS address using the PROFIBUS address switches on the Control Unit.
Figure 10-25 Example: PROFIBUS address via PROFIBUS address switch on Control Unit
492
The PROFIBUS interface is described in the following documentation:
References: /GH1/ SINAMICS S120 Equipment Manual for Control Units and Additional
System Components
– In this case, p0918 is read-only and simply displays the set address.
– A change is not effective until POWER ON.
– You can only use this method when all the PROFIBUS address switches from S1 to
S7 are set to ON or OFF.
– Address changes made via parameters must be saved in a non-volatile memory using
the "Copy from RAM to ROM" function.
– A change is not effective until POWER ON.
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5